12
8.3.3 Setting the delay time for the switching outputs
[dS1] / [dS2] = switch-on delay for OUT1 / OUT2.
►
[dr1] / [dr2] = switch-off delay for OUT1 / OUT2
►
Select [dS1], [dS2], [dr1] or [dr2] set value between 0�1 und 50 s (at 0�0
►
the delay time is not active)�
8.3.4 Setting the damping for the switching outputs
Select [dAP], set value
►
dAP-value = response time between pressure change and
change of the switching status in ms�
The value for [dAP] defines the switching frequency (f) of the output:
dAP
3
6
10
17
30
60
125
250
500
f [Hz]
170
80
50
30
16
8
4
2
1
8.3.5 Setting the output logic
Select [P-n] and set [PnP] or [nPn].
►
8.4 Service functions
8.4.1 Reading the max. value for the system pressure
Select [HI], press [Set] briefly�
►
Delete memory:
Select [HI]�
►
Press [Set] until [----] is displayed.
►
Press [Mode/Enter] briefly�
►