•  Connectors must always be closed with a counterpart. They may be left open in the field 

only briefly for servicing purposes.

Special conditions for safe operation

•  The M12 connectors were tested in accordance with table 8 of EN 60079-0 / table 5 of EN 

61241-0 for group II and for a low mechanical risk with an impact energy of 4 joules.

•  Do not separate the connectors when energized.

•  Secure the connector by tightening the nut sufficiently. Tightening torque approx. 1.2 Nm to 

1.5 Nm. This tightening torque is ensured as follows:

 -Hand-fasten the coupling nut (0.4 to 0.5 Nm).

 -Then turn by 3 notches using a screwdriver across the flats 14.

•  The connector conforms to the requirements for an M12 connector in EN 61076-2-101. 

The counterpart must also conform to this standard.

•  Always refer to the operating instructions as space restrictions may not allow markings to 

be applied to the unit.

Maintenance / Repair

The unit must not be modified nor can it be repaired. In case of a fault please contact the 

manufacturer.

The data sheets, the EC component certificates or IEC Ex component certificates are 

available from the manufacturer on request.