LED
State
Description
yellow
on
Operating status operational and ID tag de-
tected
flashes every 1.6 s alternating
with green LED
Operating status pre-operational and ID tag
detected
flashes
Device hardware fault
red
flashes every 0.4 s alternating
with other LED colours
Configuration error
flashes every 1.2 s alternating
with other LED colours
Error in the CAN bus network
on
CAN bus not accessible
flashes
LSS service active
9 Operation
9.1 CANopen interface
The read/write head has a standardised CANopen interface according to CiA
DS-301. All measured values and parameters can be accessed via the object
directory (OD). The individual configuration can be saved in the internal
permanent memory.
The device is delivered with node ID 32 and a bit rate of 125 Kbits/s.
u
Only use cables approved for CANopen.
u
Terminate the cables using terminating resistors (120 Ω).
w
The ifm cable EVC492 contains integrated terminating resistors.
9.1.1 CANopen functions
The following
• 64 transmit and receive process data objects (
1.. 64, RPDO1.. 64) in two
possible operating modes:
– individual check via remote transmission request telegram (RTR)
– event-controlled transmission
• Error messages via emergency object (
– general error register