6 Operating and display elements
6.1 Reset to factory settings
The Ethernet parameters can be reset to the factory settings . Take the following steps:
►
Remove all cable connections from the device .
►
Insert an electrically conductive bridge between pin 1 and pin 3 on the process connection IO-3 .
►
Connect the device with the voltage supply and wait until the yellow LED indication on AUX and IO-3
flashes at approx . 8 Hz .
►
Remove the conductive bridge from process connection IO-3 .
►
Disconnect the device from the voltage supply and connect it again .
> The settings are reset .
6.2 LED indicators
The device indicates the current status of the interface via the status LEDs .
6.2.1 LED AUX
LED green
LED yellow
Status
Note
off
off
no voltage supply
U
AUX
< 5 V
on
flashes at 2 Hz
voltage supply too low
5 V ≤ U
AUX
≤ 18 V
on
off
voltage supply OK
18 V ≤ U
AUX
≤ 36 V
6.2.2 LED EtherNet/IP Port 1 / Port 2
LED green
LED yellow
Status
Note
Off
Off
No connection to another Ethernet
counterpart
Link status "no link"“
On
Off
Connection to Ethernet counterpart exits,
no data exchange
Link status "link", "no traffic"
On
Flashes
sporadically
Connection to Ethernet counterpart exists,
data exchange running
Link status "link", "traffic"
6.2.3 LED Mod (module status)
LED red
LED green
Status
Note
Off
Off
No voltage supply
Check the voltage supply .
Off
Flashing
Ready for operation
Device has not yet been configured . There
is no exchange of data .
Check if the connection was established by
the EtherNet/IO scanner .
Check if Configuration Assembly was
configured .
Off
On
Normal operation
Connection to the EtherNet/IP scanner was
established and the device was configured .
Data transfer running .
Flashing
Off
Minor error
A connection to the EtherNet/IP scanner
could not be established:
- voltage error
- device could not be configured .