9
UK
SSC2 Param SP1
Setpoint 1
5���24000 pulses/min
default = 5 pulses/min
SSC2 Param SP2
Setpoint 2
3���21600 pulses/min
default = 3 pulses/min
SSC2 Config Logic
Setpoint logic / State for
target detected
NO / NC
default = NO
SSC2 Config Mode
Setpoint mode
single point / window / two-point
mode
default = single point mode
SSC2 Config Hyst
Setpoint hysteresis
10%
SSC2
Switch-On delay
Switching signal channel 2,
Switch-On delay
0���60000 ms (100 ms steps)
default = 0 ms
SSC2
Switch-Off delay
Switching signal channel 2,
Switch-Off delay
0���60000 ms (100 ms steps)
default = 0 ms
PrSC
Prescaler, indicates the
number of targets
to calculate current
revolution
1���99
default = 1
TI Select
Teach selection
SSC1 / SSC2
default = SSC1
Teach SP1
Teach switch-point 1
-
Teach SP2
Teach switch-point 2
-
Teach offset*
Sets an offset between
setpoint and current process
data value
1���200%
default = 80%
Restore Factory
Settings
Reset to factory settings
-
Delay Startup
Delay Startup
0���30000 ms (100 ms steps)
default = 15 ms
*Teach offset = defines the switch point depending on the teach process data
value�