Operating instructions AX460
36
+99999999
Highest possible final value
ANALOG GAIN (%)
With this parameter, the maximum gain can be set� The analogue gain indicates the maximum gain of the
analogue output in % referred to +/- 10 V or 20 mA�
Examples:
●
101�00 corresponds to a gain of 10�2 V / 20 mA after reaching the "Analog End“ value�
●
95�00 corresponds to a gain of 9�5 V / 18 mA after reaching the "Analog End“ value�
0�00
Lowest possible gain
100�00
Default value
110�00
Highest possible gain
ANALOG OFFSET (%)
With this parameter, the zero point shift of the output can be set�
Example: 0�20 corresponds to a gain of 0�2 V / 0�4 mA after reaching the "Analog Start“ value�
-99�99
Lowest possible zero point shift
0
Default value
+99�00
Highest possible zero point shift
9.17 Command menu
INPUT 1 ACTION
This parameter defines the control function of the Ctrl� In 1 input�
d = dynamic switching characteristics (edge evaluation), INPUT CONFIG must be set to RISING/FALLING
EDGE
s = static switching characteristics (level evaluation), INPUT CONFIG must be set to ACTIVE LOW/HIGH
NO
No function�
TARA INPUT 1
The value of input 1 is saved as OFFSET of input 1�
d
TARA INPUT 2
The value of input 2 is saved as OFFSET of input 2�
d
TARA INPUT 1+2
The value of input 1 is saved as OFFSET of input 1,
The value of input 2 is saved as OFFSET of input 2�
d
RESET TOTAL 1
The value of totalizer 1 is reset to 0�
d, s
RESET TOTAL 2
The value of totalizer 2 is reset to 0�
d, s
RESET TOTAL 1+2
The values of totalizer 1 and 2 are reset to 0�
d, s
TEACH PRESEL� 1
Value of SOURCE 1 is saved as PRESELECTION 1�
d
TEACH PRESEL� 2
Value of SOURCE 2 is saved as PRESELECTION 2�
d
TEACH PRESEL� 3
Value of SOURCE 3 is saved as PRESELECTION 3�
d
TEACH PRESEL� 4
Value of SOURCE 4 is saved as PRESELECTION 4�
d
SCROLL DISPLAY
Display change
(→ 8.2 Display during operation)
d
RESET MIN/MAX
Reset of the min� / max� values�
d, s
CLEAR LOOP TIME
N�A�