Remote I/O module 16 DI
AL4142
17
CAUTION
Exceeding the maximum input current of 16 A
w
Risk of fire
u
I
U
and I
A
of the supply voltages US and UA accordingly, taking into account the derating
behaviour of the device:
u
Disconnect power.
u
Connect the device via port XD1 to the US supply voltage with 24 V DC (20…30 V SELV/PELV).
u
Optional: Connect the device via port XD1 to the UA supply voltage with 24 V DC (20…30 V SELV/
PELV).
u
For connection, use an L-coded M12 connector (with at least protection rating: IP65 / IP66 / IP67).
u
Tighten the cable sockets according to the torque specifications indicated by the cable
manufacturer. Maximum permissible tightening torque: 0.8 Nm
Wiring:
3
1
4
2
5
1: +24 V DC (US)
2: GND (UA)
3: GND (US)
4: +24 V DC (UA)
5: FE
6.5.1 Derating behaviour
The current I
US
available at ports X1...X8 and the currents I
US-daisy-chain
and I
UA-daisy-chain
available at port
XD2 depend on the ambient temperature of the device.
6.5.1.1 Derating without daisy chain
-40 -30 -20 -10 0 10 20 30 40 50 60 70
1
2
3
4
2000 m
3000 m
4000 m
Current [A]
Temperature [°C]
0.5
1.5
2.5
3.5
1