IO-Link Master with Modbus TCP Interface DataLine 4 Ports IP 65 / IP 66 / IP 67
66
>
9.3.3
Set IO-Link ports
34460
Register area for the access to the configuration of the IO-Link ports:
→
Configuration Area
(
The area contains the following data:
Operating mode of IO-Link ports
Device validation and Data storage settings
Failsafe values of outputs
► Observe the general rules for access to the Modbus registers (→
Rules for accessing the
Modbus registers
(
))!
► When writing several registers at conce, ensure that the transferred parameter data has
the correct length!
Register
Contents
Access
9000
Port X01: Port Configuration
r/w
9006
Port X02: Port Configuration
r/w
9012
Port X03: Port Configuration
r/w
9018
Port X04: Port Configuration
r/w
r/w = read and write
In addition, the user can set the IO-Link ports of the AL1340 via the following acyclic commands:
"Set Mode":
→
Command 0x10
– Set mode
(
"Set Validation ID / Data Storage":
→
Command 0x20
– Set validation ID / data storage
(
"Set Fail-safe Data Pattern":
→
Command 0x30
– Set fail-safe data pattern
(
The commands use the process mechanisms of the acyclic command channel (
→
Use acyclic
services
(