Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100)
2017-08-18
Function
>
4.2
Digital inputs
7584
The device has 4 additional digital inputs (type 2 according to EN 61131-2).
The digital inputs are on pin 2 of the IO-Link ports X01 ... X04.
All inputs refer to the potential of the device supply (pin 3).
>
4.3
IO-Link supply
7623
The device has 4 supplies for IO-Link devices (sensors, actuators).
The IO-Link ports X01...X04 are ports class A.
Every supply provides short circuit monitoring.
The device ensures fire protection for the connected IO-Link devices by providing a power-restricted
circuit at the IO-Link ports (according to IEC61010-1 and Class 2 according to UL1310).