IO-Link Master with AS-Interface Interface StandardLine 2 Ports IP 65 / IP 66 / IP 67
58
>
Mapping: Status information
59349
Basic
slave
channel
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
reserved
SC:
X01/
X02
1
Port X01: PQI
reserved
PCE res. CMD
Req
CMD
Resp
2
reserved
Port X02: PQI
3
Number of Events in Buffer
reserved
Legend:
SC
Short Circuit: indicates whether there is a short circuit on at least
one of the two IO-Link ports
1 bit
0x0
no short circuit
0x1
short circuit
CMD Resp Command Response: indicates whether the acyclic command
channel (response) contains valid data and whether it can be read
1 bit
0x0
not ready
0x1
ready
CMD Req
Command Request: indicates whether the acyclic request channel
(request) is valid
1 bit
0x0
not valid
0x1
valid
PCE
Port Configuration Error: indicates whether projected values for
"Vendor ID" and "Device ID" correspond with the values of the
IO-Link devices on the IO-Link port
1 bit
0x0
no error
0x1
error
PQI
Port Qualifier Information: Status and diagnostic information of the
IO-Link port
1 byte
→
Mapping: PQI
(
→
Number of
Events in
Buffer
Number of events in the buffer memory
1 byte 0x00...0x0C