IO-Link Master with AS-Interface Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
15
>
6.3
Connecting the unit
51961
The AS-i voltage supplies the communication electronics.
►
Connect the AS-i voltage input to AS-i power supplies only!
The AUX voltage supplies the IO-Link master.
►
In case of cables that are longer than 25 m, take the voltage drop and the necessary
minimum supply voltage of 20 V into consideration!
►
Disconnect power.
►
Connect the device via the M12 socket to the AS-i supply voltages
AS-i (18...31,6 V DC) and AUX (24 V DC (20...300 V SELV/PELV)).
Tightening torque: 0.6...0.8 Nm.
Recommended maximum cable length: 25 m
►
To connect the device, use M12 connectors with at least protection
rating IP 65 / IP 66 / IP 67 (
→
Accessories
(
→
Optional: Supply of an additional AS-i device (daisy chain)
►
Connect an additional AS-i device to the M12 socket X22 of the
AC6000 (loop-through function).
Tightening torque: 0.6...0.8 Nm
Recommended maximum cable length: 25 m
►
To connect the device, use M12 connectors with at least protection
rating IP 65 / IP 66 / IP 67 (
→
Accessories
(
→