Operating instructions  

AS-i SmartLine FO repeater

AC3227

80272533/00

    

 01/2018

UK

Содержание AC3227

Страница 1: ...Operating instructions AS i SmartLine FO repeater AC3227 80272533 00 01 2018 UK ...

Страница 2: ...ments 4 5 Installation 5 5 1 Installation of the device 5 5 2 Remove device 5 6 Connections 6 6 1 Electrical connection 6 6 2 Optical fibre connection 7 7 Terminal connection 7 8 Operation LEDs 8 9 Example of an AS i topology 8 10 Maintenance repair disposal 8 10 1 Maintenance 8 10 2 Cleaning the housing surface 8 10 3 Disposal 8 ...

Страница 3: ...rty may occur The manufacturer assumes no liability or warranty for any consequences caused by tampering with the product or incorrect use by the operator Installation electrical connection set up operation and maintenance of the product must be carried out by qualified personnel authorised by the machine operator The plant operator is responsible for the safety of the plant in which the device is...

Страница 4: ...o repeater 1 A system consists of two AS i FO repeaters Electrical separation of the incoming AS i line from the outgoing AS i line Additional AS i power supply required Connection via supplied COMBICON connectors Use of a standard fibre optic cable with ST connector 4 Operating and display elements 4 1 LED 2 Rx Tx 3 1 COMBICON connector with cage clamps 2 Panel for labelling 3 Connection fibre op...

Страница 5: ... space between the device and the top and bottom of the control cabinet to enable air circulation and to avoid excessive heating Take into account the internal heating of all devices when mounting several devices side by side and observe the environmental conditions for every device 5 2 Remove device ...

Страница 6: ... line If the AS i FO repeater 1 is at the cable end of an AS i line and the cable length is 100 m the AS i bus must be terminated with a link between T1 and T2 A link is supplied The AS i bus termination is used to improve the signal quality and to extend the AS i network cable Only one AS i bus termination may be used per AS i segment Activate the termination and check the signal quality of the A...

Страница 7: ...5 µm with ST connector recommended up to 500 m Fibre optic cable 62 5 125 µm with ST connector do not use at distances below 200 m Observe permissible bending radii of the fibre optic cable manufacturers Calculation of the achievable distances for data transmission ifm fibre optic calculator in the download area 7 Terminal connection A A A A Line AS i T1 T2 Line Termination Rx Tx A AS i A AS i A A...

Страница 8: ...cable 100 200 m R S S PS M master PS power supply S slave R repeater T termination terminating resistor for cable length 100 m 10 Maintenance repair disposal 10 1 Maintenance The device is maintenance free 10 2 Cleaning the housing surface Disconnect the device Clean the device from dirt using a soft chemically untreated and dry cloth Micro fibre cloths without chemical additives are recommended 1...

Страница 9: ...9 UK ...