7.1  Activation of the periphery fault message of the channels 

1 to 4

By means of the parameter bits P1 and P2 you can define which measuring 

channels can trigger a peripheral fault message (see table).

But irrespective of the defined parameters all 4 channels are always transferred 

via the AS-Interface�

8  Measuring range

 

For the measuring ranges please refer to the following tables�

Range

-200...850 °C

Units

dec.

Units

hex.

LED  

analo-

gue

Meaning

 < -219�4 °C

32767

7FFF

flashing

short circuit

-219�4 °C���-200�1 °C -2194 ��� -2001 F76E ��� F82F on

below nominal 

range

-200 °C���850 °C

-2000 ��� 8500

F830���2134

on

nominal range

850�1 °C���883�6 °C

8501 ��� 8836

2135 ��� 2090 on

above nominal 

range

> 883�6 °C

32767

7FFF

off

wire break

8.1  Transmission time of the analogue values

The transmission time of the analogue values depends on the conversion 

time of the analogue signals into digital signals in the AS-i module and on the 

transmission time via the AS-Interface�
The conversion time for 4 Pt100 signals is 480 ms�
The transmission time of the 4 16-bit values via the AS-interface ideally is 7 

AS-i cycles per value� For a cycle time of 5 ms per AS-i cycle this results in a 

transmission time of 4 x 7 x 5 ms = 140 ms via the AS-Interface�
Thus the total transmission time for 4 temperature values ideally is 480 ms 

(conversion time) + 140 ms (transmission time) = 620 ms.

Содержание AC3222

Страница 1: ...Operating instructions AS i SmartLine module AC3222 80255919 00 01 2017 UK...

Страница 2: ...rical connection 6 6 1 Wiring 6 6 1 1 Connection of a 2 wire Pt100 element 7 6 1 2 Connection of a 4 wire Pt100 element 7 7 Parameter setting 8 7 1 Activation of the periphery fault message of the cha...

Страница 3: ...or the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Functions and features If the operating instructions or the techni...

Страница 4: ...f measured values for 4 channels 480 ms Resolution 16 bits 0 1 C Measuring range 200 850 C AS i profile S 7 3 E Connection of 2 wire and 4 wire sensors possible Maximum number of modules per AS i syst...

Страница 5: ...ace between the unit and the top and bottom of the control cabinet to enable air circulation and to avoid excessive heating Take into account the internal heating of all devices when mounting several...

Страница 6: ...ations for the installation of electrical equipment must be adhered to Disconnect power Connect the unit 6 1 Wiring S sensor inputs S sensor inputs 1 4 drive outputs 1 4 drive outputs FE functional ea...

Страница 7: ...exact results than 2 wire sensors provi ded that the wire resistance is the same The changeover between 2 and 4 wire sensors is made via the parameter bit P3 Connect at least one Pt100 sensor prior to...

Страница 8: ...ment all contact resistances and connection resistances add up by measurement and can falsify the measurement result 7 Parameter setting Parameter bit Designation Description Comments P0 Filter 1 50 H...

Страница 9: ...000 8500 F830 2134 on nominal range 850 1 C 883 6 C 8501 8836 2135 2090 on above nominal range 883 6 C 32767 7FFF off wire break 8 1 Transmission time of the analogue values The transmission time of t...

Страница 10: ...heral fault is indicated if at least one of the signals I1 I2 I3 or I4 is outside the measuring range or if nothing is connected to at least one analogue channel 10 Maintenance repair disposal 10 1 Ma...

Страница 11: ...11 UK 11 Scale drawing 108 35 25 4 93 126 LED...

Отзывы: