AS-i Gateway with Profinet device interface
79
>
5.5.4
System: Diagnosis
9053:
The [Diagnosis] menu item provides access to the diagnostic data of the device.
>
Display diagnostic data
41435
To display the diagnostic data of the device:
1 Select menu page
►
>
2 Display diagnostic data
>
Page shows the following information:
Name
Description
Possible values
[Betriebszeit
[JJ-TTT SS:MM]]
Operating time of system and
components
All times indicated in [JJ-TTT-SS-MM] format:
YY = years
DD = days
hh = hours
mm = minutes
[gesamt]
Operating time of device
[aktuell]
Operating time of device since last
system start
[LCD]
Operating time of LCD
[PLC]
Operating time of controller
[Temperatur]
Current device temperature
Indications in [°C] (
→ Note)
[Versorgt durch]
Voltage supply of device
[Aux]
Voltage is supplied separately by AS-i
network and AUX 24 V.
[AS-i]
Voltage is only supplied by the AS-i
network.
[Power Modul]
Voltage is supplied by data decoupling
module.
The temperature monitoring continuously checks the system temperature of the device. The
following temperature ranges apply:
Normal range: < 79.9 °C
Limit range: 80 °C ... 84.9 °C
Critical range: >= 85 °C
If the system temperature reaches the critical zone, a warning is displayed in the
→
Online
Support Center (OSC)
(
). The warning only disappears when the device temperature is
again in the normal range.