background image

9

UK

7  Set-up and settings for water

(For media other than water → 8.1: Low flow adjustment).

 

Switch on the supply voltage�

 

> All LEDs light and go out again step by step� During this time the output is 

closed (if configured as normally open)� The unit is in the operating mode�

 

Let the normal flow circulate in the installation�

 

Check the display and determine further actions�

1

         

The factory setting is suitable for the applica-

tion� 

 

No further settings are required�

2

         

Your normal flow is below the representation 

range of the display�

2 setting options: 

 

► Change the switch point (→ 7.1).

 

► Carry out high flow adjustment (→ 7.2).

3

         

Your normal flow exceeds the representation 

range of the display  (LED 9 flashes)�

 

► Carry out high flow adjustment (→ 7.2). 

You can restore the factory setting any time. (→ 8.3).

7.1  Change the switch point (optional)

For the factory setting the switch point is at LED 7� A change makes sense in the 

folowing cases:

•  the display shows example 2�

•  the flow fluctuates much or pulsates�

•  a faster response time of the unit is requested (low switch point = fast response 

with rising flow, high switch point = fast response with falling flow)� 

 

Briefly press the pushbutton 

 or  �

 

> The switch point LED flashes�

 

Press the pushbutton 

 or   as often as required� Each press of the push-

button shifts the LED by one position in the indicated direction�

Note:  If no pushbutton is pressed for 2 s, the unit returns to the operating mode 

with the newly set value�

Содержание SI0562

Страница 1: ...Operating instructions Flow monitors SI5006 SI0562 704194 04 02 2022 UK...

Страница 2: ...stem 6 4 3 Mounting operation 6 5 Electrical connection 7 6 Operating and display elements 8 7 Set up and settings for water 9 7 1 Change the switch point optional 9 7 2 High flow adjustment optional...

Страница 3: ...icable for any service personnel authorised by the manufacturer of the system Read this document before setting up the product and keep it during the entire service life The product must be suitable f...

Страница 4: ...case of need you can change the output to normally closed 8 2 It then applies output open if medium is flowing If the flow speed increases the switching status changes when the switch point is reache...

Страница 5: ...lation location General The sensor tip is to be completely sur rounded by the medium Insertion depth of the sensor minimum 12 mm Recommended For horizontal pipes mounting from the side For vertical pi...

Страница 6: ...rces of interference 4 3 Mounting operation Ensure that the system is free of pressure during installation Ensure that no media can leak at the mounting location during installa tion Grease the thread...

Страница 7: ...ast acting The permissible potential difference between supply and output circuit is max 300 V The metal parts of the housing must be properly grounded For this you can for example attach a grounding...

Страница 8: ...For information about available sockets go to www ifm com 6 Operating and display elements 1 Operation display The green LEDs indicate the current flow the LEDs 0 to 9 represent the range between no...

Страница 9: ...ur normal flow exceeds the representation range of the display LED 9 flashes Carry out high flow adjustment 7 2 You can restore the factory setting any time 8 3 7 1 Change the switch point optional Fo...

Страница 10: ...en Let the normal flow circulate in the installation Press the pushbutton and keep it pressed LED 9 lights after approx 5 s it flashes Release the pushbutton The unit is now adapted to your flow condi...

Страница 11: ...of need you can change the output to normally closed Press the pushbutton for at least 15 s LED 0 lights after approx 5 s it flashes After 10 s the current setting is displayed LEDs 5 9 light orange o...

Страница 12: ...then passes into the operating mode with unchanged values Possible cause aid Error during installation Read chapter 4 Installation Check whether all requirements have been met The difference between...

Страница 13: ...output closed LED red output open LED 9 flashes current flow above the representation range LED 0 flashes current flow far below the represen tation range Interference indicators Display OFF no LED li...

Отзывы: