Select [LED] and set the display function for the digital display and LED
ring:
-[SPRP]: One LED on the LED ring indicates the set point and a second
LED the reset point�
-[HInd]: 2 adjacent LEDs on the LED ring mark the lag indicator for
maximum value ([HInd], high indication)�
-[LInd]: 2 adjacent LEDs on the LED ring mark the lag indicator for
minimum value ([LInd], low indication)�
To reset:
►
Touch [Set] for 1 second�
> The two LEDs jump to the current position of the pointer�
-[Ph]: Display of pulsating signals and pressure peaks:
-In case of quick pressure changes (quickly pulsating signals) the
digital display and LED ring indicate the minimum value and the
maximum value�
-In case of one-time short pressure peaks the digital display and LED
ring show the indication for a longer time�
-[Pdir]: The LED ring indicates the trend of the pressure changes (5
LEDs below the pointer for rising pressure; 5 LEDs above the pointer
for falling pressure)�
A damping set with dAP or dAA also has an effect on this display�
9.3 Set output signals
9.3.1 Set output functions
►
Select [OU1] and set the switching function:
-[Hno] = hysteresis function/NO�
-[Hnc] = hysteresis function/NC�
-[Fno] = window function/NO�
-[Fnc] = window function/NC�
►
Select [OU2 ] and set the analogue function:
-[I] = current signal proportional to pressure 4…20 mA�
-[InEG] = current signal proportional to pressure 20…4 mA�
9.3.2 Set switching limits
►
Select [SP1] and set the value at which the output switches�
►
Select [rP1] and set the value at which OUT1 switches off�
rP1 is always smaller than SP1� The unit only accepts values which are
lower than SP1�