1 Safety instructions

•  Please read the product description prior to installing the unit.
•  Ensure that the product is suitable for your application without any restrictions.
•  If the operating instructions or the technical data are not adhered to, personal 

injury and/or damage to property may occur.

•  Please check for all applications that the product materials (see Technical data) 

are compatible with the media to be measured.

•  Use in gases at pressures > 25 bar only after contacting the manufacturer ifm.
For units with cULus approval and the scope of validity cULus:

The device shall be supplied from an isolating transformer having a secondary 

Listed fuse rated as noted in the following table.

Overcurrent protection

Control-circuit wire size

Maximum protective device rating 

Ampere

AWG

(mm

2

)

26

(0.13)

1

24

(0.20)

2

22

(0.32)

3

20

(0.52)

5

18

(0.82)

7

16

(1.3)

10

The Sensor shall be connected only by using any R/C (CYJV2) cord, having 

suitable ratings.

Contents

1 Safety instructions ................................................................................................2

2 Function and features ...........................................................................................3

2.1 Applications ....................................................................................................3

3 Installation ............................................................................................................4

4 Electrical connection.............................................................................................4

5 Scale drawing .......................................................................................................5

6 Technical data .......................................................................................................6

Содержание PA32xx Series

Страница 1: ...Installation Instructions Electronic pressure sensor PA32xx 704091 01 08 2010 UK ...

Страница 2: ...es 25 bar only after contacting the manufacturer ifm For units with cULus approval and the scope of validity cULus The device shall be supplied from an isolating transformer having a secondary Listed fuse rated as noted in the following table Overcurrent protection Control circuit wire size Maximum protective device rating Ampere AWG mm2 26 0 13 1 24 0 20 2 22 0 32 3 20 0 52 5 18 0 82 7 16 1 3 10 ...

Страница 3: ...4 5 10 145 30 450 PA3228 0 0 25 0 3 63 10 145 30 450 MPa bar 10 kPa bar 100 Static and dynamic overpressures exceeding the indicated overload pressure are to be avoided by taking appropriate measures The indicated bursting pressure must not be exceeded Even if the bur sting pressure is exceeded only for a short time the unit can be destroyed NOTE Risk of injury Use in gases at pressures 25 bar onl...

Страница 4: ...ten firmly 4 Electrical connection The unit must only be connected by an electrician The national and international regulations for the installation of electrical equipment must be observed Voltage supply to EN50178 SELV PELV Disconnect power Connect the unit as follows Core colours of ifm sockets 1 BN brown 2 WH white 3 BU blue 4 BK black n c not connected ...

Страница 5: ...5 UK 5 Scale drawing PA3221 PA3228 PA3220 Dimensions are in millimeters ...

Страница 6: ...ton Operating temperature C 25 80 Medium temperature C 25 902 Storage temperature C 40 100 Protection PA3220 PA3222 IP 68 IP 69K Protection PA3223 PA3228 IP 65 Protection class III Insulation resistance MΩ 100 500 V DC Shock resistance g 50 DIN IEC 68 2 27 11 ms Vibration resistance g 20 DIN IEC 68 2 6 10 2000 Hz EMC EN 61000 4 2 ESD 4 kV CD 8 kV AD EN 61000 4 3 HF radiated 30 V m EN 61000 4 4 Bur...

Отзывы: