11.3 Error indications
Table
11-2
Possible cause
Recommended measures
[Err]
Fault in the electronics.
►
Replace the unit.
[SEnS]
• Interfering sources (e.g. EMC)
• Poor cables
• Supply voltage disturbed
►
Check electrical connection.
►
Check connection between the
sensor and the tank ground.
[FAIL]
Error during adjustment of the
overflow prevention OP:
• Overflow prevention covered by
the medium during adjustment.
• Overflow prevention soiled.
• Minimum distances too short
• Mounting element detected
below the overflow prevention.
• Measured value not constant.
►
Lower the level, if possible.
►
Clean the probe.
►
Observe the notes on installation.
►
Correct the position of the overflow
prevention OP.
►
Repeat the adjustment.
►
Deactivate OP
(→ 5.2.1)
[SC1] + LED 8
Flashing: short circuit in
switching output
OUT1.
►
Remove the short circuit.
[PArA]
Faulty data set.
►
Reset to factory settings [rES].
11.4 Output response in different operating states
Table
11-3
OUT1
OUT2*
Initialisation phase
OFF
0 mA
Overflow prevention OP
not adjusted
OFF
3.5 mA
Overflow prevention OP
adjusted or deactivated,
normal operation
according to process value
and
[ou1] setting
according to process value
4...20 mA
Fault
OFF with [FOU1] = [OFF]
ON with [FOU1] = [On]
< 3.6 mA with [FOU2] = [OFF]
> 21 mA with [FOU2] = [On]
* If the output function [ou2] = [I] has been selected