10
7 Programming
1
Mode/Enter Set
Press the Mode/Enter button several
times until the respective parameter is
displayed�
2
Mode/Enter Set
Press the Set button and keep it pressed�
The current parameter value flashes
for 5 s,
then the value is increased* (incremental
by pressing briefly or scrolling by holding
pressed)�
3
Mode/Enter Set
Press the Mode/Enter button briefly (=
acknowledgement)�
The parameter is displayed again, the set
parameter value becomes effective�
4
Change more parameters:
Start again with step 1�
Finish programming:
Wait for 15 s or press the Mode/Enter
button until the current measured value is
indicated again�
*Decrease the value: Let the display of the parameter value move to the maximum setting
value� Then the cycle starts again at the minimum setting value�
Timeout: If no button is pressed for 15 s during the setting procedure, the unit
returns to the run mode with unchanged values�
The unit can be electronically locked to prevent unwanted adjustment of the set
parameters: Press (in Run mode) both setting buttons for 10 s� As soon as the
indication goes out the unit is locked or unlocked�
Units are delivered from the factory in the unlocked state�
With the unit in the locked state
is indicated briefly when you try to change
parameter values�