2

Function and features 

The airflow monitor monitors airflows. It senses whether there is a preset airflow 
(= green LED lights, output relay energised for NO function, de-energised for NC 
function). 
If the flow is below the preset value, the red LED lights. The output relay is de-
energised for NO function and energised for NC function.

Setting range 1 m/s to 10 m/s.

• 

Start-up delay of 3 s ... 60 s (to suppress short-time fluctuations), depending on 

• 

the preset value

Mounting

Mount the airflow monitor by means of the mounting clamp provided. Diameter of 
the mounting hole for the unit: 24 mm. If mounting is to be airtight, use the gasket 
provided. The sensing head must be completely immersed into the airflow and 
should be in the range of the highest flow velocity, if possible. Installation depth: 
min. 32 mm, max. 120 mm.

min. 32 mm

max. 120 mm

Align the unit in the airflow; the arrow on the cap must point in the direction of flow.

arrow

(must be at the top)

Poti

Poti

LEDs

LEDs

arrow