Installation Instructions
Airflow monitor
SL0106
704565 / 00
02 / 2009
UK
Страница 1: ...Installation Instructions Airflow monitor SL0106 704565 00 02 2009 UK ...
Страница 2: ...s 60 s to suppress short time fluctuations depending on the preset value Mounting 2 Mount the airflow monitor by means of the mounting clamp provided Diameter of the mounting hole for the unit 24 mm If mounting is to be airtight use the gasket provided The sensing head must be completely immersed into the airflow and should be in the range of the highest flow velocity if possible Installation dept...
Страница 3: ...e type label Justieren 4 setting potentiometer sensitivity LEDs 1 Apply the operating voltage Switch on the flow preset value and keep it constant In case of a cold start wait until the stabilisation time of approx 60 s is over 2 If the red LED lights turn the pot slowly clockwise until the red LED goes off and the green LED comes on If the green LED lights turn the pot slowly anticlockwise until ...