6
5.2 Mounting
The unit is mounted using a mounting clamp or an adapter� The following standard
mounting accessories are available:
Order no� Material
E43000
mounting clamp (for non-pressurised tanks)
E43001
flange plate 73-90 with clamp adapter (pressure rating of 0�5 bar)
E43002
welding adapter with clamp adapter (pressure rating of 0�5 bar)
E43003
mounting adapter G¾ with clamp adapter (stainless steel, pressure rating of 0�5 bar)
E43004
mounting adapter G1 with clamp adapter (stainless steel, pressure rating of 0�5 bar)
E43005
flange plate 100-125 with clamp adapter (aluminium, pressure rating of 0�5 bar)
E43006
flange plate 65-80 with clamp adapter (aluminium, pressure rating of 0�5 bar)
E43007
flange plate 54 - 52x52 with clamp adapter (aluminium, pressure rating of 0�5 bar)
E43016
mounting clamp with mounting bracket (for non-pressurised tanks)
E43019
mounting adapter G¾ with clamp adapter (brass, pressure rating of 0�5 bar)
Further accessories on request�
5.3 Set the installation depth
S
A = response level
H = tank height
L = probe length
L1 = installation depth
L2 = extension length
L3 = mounting length (min�: 60 mm)
M = height mounting adapter
MET = max� immersion depth
(Active zone) = 31 mm
S = height of the boss
► Select the installation length L1 so that at least half the MET zone is covered
when the response level A has been reached, that is:
L1 = (H - A) + ½ MET + S�
The unit switches when the level reaches the MET zone� The exact position
(exact response level) depends on the following factors:
● characteristics of the medium�
● Installation conditions�
● adjustment of the unit (→ 8 Settings).