8. Window technology
The output is only enabled in case of a damping between 3 mm and
7 mm (zone 2, see 11. Technical data, page 17).
In the zones 1, 3 and 4 the output remains switched off.
The safe switching off distance is 14 mm.
Note
The enable zone is specified for the described environmental condi-
tions or conditions of use (please see 11. Technical data, page 17).
Conditions of use outside the given technical data result in a differ-
ent enable zone.
9. Response times
(removal from the enable zone)
15
ENGLISH
3
7
14
1
2
3
4
0
mm
fail-safe switch
damping element
enable
zone
Change of zones
Response time (max.)
from
to
2
3
80 ms
2
1
360 ms
2
4
20 ms