IFM Electronic DI502x Скачать руководство пользователя страница 1

Installation instructions

Compact speed monitor M30 

DC version

 DI502x 

 DI52xA

80258280 / 00

 

12 / 2016

UK

Содержание DI502x

Страница 1: ...Installation instructions Compact speed monitor M30 DC version DI502x DI52xA 80258280 00 12 2016 UK ...

Страница 2: ...es 4 3 1 Switching function normally open 4 3 2 Switching function normally closed 4 3 3 Damping 5 3 4 Function diagram 5 3 5 IO Link 6 4 Mounting 6 5 Electrical connection 7 5 1 Wiring 7 6 Setting 7 6 1 Setting for switching function normally open 8 6 2 Setting for switching function normally closed 8 7 Operation 8 8 Technical data 9 ...

Страница 3: ...r maintenance of the device Read this document before use to familiarise yourself with operating conditions installation and operation Keep this document during the entire duration of use of the device WARNING Adhere to the warning notes and safety instructions 2 Safety instructions 1 1 Symbols and warnings used Instructions Cross reference Information Supplementary note Important note Non complia...

Страница 4: ...see delivery note or manufacturer see cover sheet back The ATEX protection is ensured even without mechanical protection 3 Functions and features The compact non contact inductive speed monitor detects when a speed drops below a pre set value and signals this with a switched output 3 1 Switching function normally open Transistor output LED green switched conducting on rotational speed SP Hy and du...

Страница 5: ...mally open 4 Switching function normally closed SP switch point Hy hysteresis transistor output switched conducting The start up delay suppresses an error signal as long as the machine is in the process of starting and has not yet reached its minimum speed After application of the operating voltage the start up delay is active only once If the plant is started and stopped frequently linking the dr...

Страница 6: ...will find the IODDs necessary for the configuration of an IO Link device and detailed information about parameter setting tools process data structure diagnostic information and parameter addresses at www ifm com gb io link 4 Mounting Mounting principle Mounting specifications Fix the unit using a bracket and secure it by means of the nuts provided so that it cannot work loose Flush installation A...

Страница 7: ...brown BU blue L L BN BK BU L L BN BK BU DI5026 DI523A BK switching output IO Link PNP NPN programmable 6 Setting 1 2 2 1 Multi turn potentiometer for switch point setting without end stop 2 LEDs Green LED for switching status indication 3 1 Switching function normally open Yellow LED for damping indication input signal 3 3 Damping Operating and display elements ...

Страница 8: ...the pot slowly anticlockwise until the green LED lights Setting is finished 6 2 Setting for switching function normally closed When the green LED lights Turn the pot slowly anticlockwise until the green LED goes out Setting is finished When the green LED does not light Turn the pot clockwise until the green LED lights Turn the pot slowly anticlockwise until the green LED goes out Setting is finish...

Страница 9: ... 20 22 20 22 Current rating mA 250 Voltage drop V 2 5 Reverse polarity protection yes Short circuit protection yes Overload protection yes Nominal sensing range Sn mm 10 Operating distance mm 0 8 1 Setting range pulses min 5 3600 Via potentiometer Via IO Link Hysteresis of SP 10 Damping frequency pulses min 18000 Switching function NO Switching function NC ...

Страница 10: ...30 Ambient temperature C 25 80 20 60 Protection IP 65 IP 67 III ATEX equipment category 3D IO Link Connection PUR cable 2 m 3 x 0 5 mm applicable programmable not applicable Data sheets and EC declarations of conformity can be found at www ifm com Data sheet search Article number ...