Operating Instructions IO-Link Master with EtherNet/IP interface StandardLine 8 Ports IP 65 / IP 67 (AL1122)
2017-05-31
Electrical connection
>
6.3
Connect the device
2580
► Disconnect power.
► Connect the device via M12 socket X31 to 24 V DC
(20...30 V SELV/PELV;
according to EN61010-1, secondary circuit
with maximum 30 V DC derived from applied voltage up to 300 V
of overvoltage category II).
Tightening torque: 0.6...0.8 Nm
Maximum cable length: 25 m
► To connect the debice , use M12 connectors with protection rating
IP 65 / IP 67 or higher (e.g. EVC708).
If the port X01...X08 will be used as IO-Link ports Class B:
► Connect adapter for Port Class B operation to 24 V DC (20...30 V
SELV/PELV) (
→
IO-Link ports
(