About Advanced Features & Operation
OUTSIDE SENSOR - To view an Outside Sensor
(step #12, page 21)
, enter the Advanced Setup by
pressing and holding the MODE button. While
holding MODE, press the FAN button for 5 seconds
to enter Setup screens. Advance to setup step #12
by repeatedly pressing the MODE button. If an
optional outside sensor is connected, the outside
temperature will appear in the clock display.
REMOTE SENSOR
(P/N G100-71520313)
- The
thermostat is programmed from the factory to auto-
Page 32
matically recognize when a Remote
Sensor is connected (
step #12, page
21).
The Remote Sensor measures indoor
air temperature and sends this infor-
mation to the thermostat; it measures
temperature with a range of 32 to
99 F.
The Remote Sensor should be con-
nected to the thermostat using solid
conductor CAT 5, CAT 5e, or CAT 6 type network
communication cable. This is an unshielded cable with
four twisted pairs of 24 gauge solid wire;
DO NOT use
stranded cable
. The cable length should not exceed
250 feet. If less than 75 feet of cable is required to
connect the thermostat to the Duct Sensor, a three
conductor thermostat cable (18-24 gauge) may be
used; this cable is NOT suitable for any length greater
than 75 feet.
Important: Do not use shielded wire. Do not run sensor wiring in
the same conduit as the 24vac wiring. Electrical interference
may cause the sensor to give incorrect temperature readings.