Output Test Menu

  

 
Zolar has a built-in Output Test Menu to confirm operation of each Output circuit after installation or to 
troubleshoot suspect systems. In order to enter the Output Test Menu, you must simultaneously press all 
four buttons for one second continuously. Zolar will then respond with the following prompt: 
 

OUTPUT TEST MODE: WEEP #1 OFF 

 
You can change the state of the indicated Output by pressing the 

+/Yes

  key to turn the Output On or 

by pressing the 

-/No

  key to turn the Output Off.  Press the 

Next 

 key to test the next Output. As you 

move on to each next Output, the prior one will automatically turn Off.  
 
During the time you use the Output Test Menu all other normal Sensing and Output functions are 
temporarily halted. If there has been no further key press for at lest 60 seconds, any Output currently 
turned On will be turned Off and the normal functions of Zolar will restart. 
 
 
 

Serial Data Port

  

 
Zolar is optionally equipped with an RS-232 serial data port for use with remote configuration and data acquisition 
computer applications. IDX intends to offer such applications in the future. The protocol for communication is 
proprietary and will be shared with other OEM equipment manufacturers on request. 
 
 

Autodialer Interface

  

 
The Zolar Autodialer Enable output is an open-collector NPN transistor that sinks current to Common when activated in 
an alarm situation. Most all autodialers on the market will work with this type of output as it is compatible with a N.O. 
relay or switch contact. IDX recommends one of the two autodialers below… or their successor models. The manuals 
for these products can be downloaded from the IDX Web site from the Autodialer page. 
 

Visonic DL-125C 

Connect the Visonic DL-124C autodialer as 
shown in their manual in Figure 5 of 
section 3.2 on page 2 as shown to the right. 
Connect the “-” terminal on the DL-125c to 
Zolar’s “Autodialer Com” terminal and 
their "Z-1" terminal to Zolar’s “Autodialer 
Enable” terminal.  The dialer channel 1 
must be configured as N.O. (normally open 
- factory default) as indicated in the manual 
on page 5, location 22. Please refer to the 
Visonic manual for other programming and 
operation information. A link to a PDF 
copy of the manual can be found on the 
Zolar Web page. 
 
  

United Security Products AD-2001 

Connect the AD-2001 “1” terminal to the Zolar “Autodialer Enable” and the AD-2001 “C” terminal to the Zolar 
“Autodialer Com” terminal. One must additionally configure Channel 1 as N.O. and Momentary. See the AD-2001 
manual pages 5 and pages 10 to 11 for more details. A link to a PDF copy of the manual can be found on the Zolar Web 
page. 

Содержание Zolar Z440

Страница 1: ... cover label near the input power terminals indicates the configuration of the unit Expanded Output Option One each Weep and Auxiliary Outputs are included in the Standard Configuration One each additional Weep and Auxiliary outputs may be added to the Standard Configuration to provide sensing and control for larger carwashes having additional functions or services When the Expanded Output Option ...

Страница 2: ... Z440LP Light Probe to Sensor 2 terminals and use the front panel Configuration Menu to configure Aux 1 Output for control by Light The Light Probe will ensure that lights are turned on and off as needed no matter what time of year it is or how thick the clouds are See the Light Probe Application Note for useful information in using this function Time Of Day Control Equipment such as an office air...

Страница 3: ...r LEDs are On when their corresponding outputs are On Configuration Menu Just below the dot matrix LED display window is a set of four buttons shown above for navigating the Configuration Menu If the Next or Back keys are pressed the status message is interrupted and the Configuration Menu is entered From the Configuration Menu all time temperature or light threshold set points can be viewed by su...

Страница 4: ... to the Start Weep and Full Weep set points as detailed in the diagram on page 2 In the example using Start Weep 34 F and Full Weep 15 F if the sensed temperature is 20 F then we would be 5 from Full Weep out of a total of 19 between Start Weep and Full Weep Since at Start Weep the relay is On 100 of the time then at 20 F the relay would be On 5 19 26 3 of the time during each minute for a period ...

Страница 5: ...Blower output will be active low At temperatures below the set point the Foam Blower output will be inactive Once the Foam Blower becomes active the temperature must rise 2 F above the set point before the output will switch to inactive 2 hysteresis The Yes and No keys will modify the set point and the Next key will save the values and advance to the menu to the alarm parameters TEMP 1 ALARM LOW F...

Страница 6: ...anufacturers on request Autodialer Interface The Zolar Autodialer Enable output is an open collector NPN transistor that sinks current to Common when activated in an alarm situation Most all autodialers on the market will work with this type of output as it is compatible with a N O relay or switch contact IDX recommends one of the two autodialers below or their successor models The manuals for the...

Страница 7: ...ng RED to Sensor BLK to Reference SHLD To Shield Z440LP For Bay Lighting Z440TP For Weep Tunnel Z440TP For Slab Heater Z440TP For Weep Bays Contactor To Bay Lights Solenoid To N O Tunnel Weep Valve Solenoid To N O Bay Weep Valve Contactor To Slab Heater Pump 120VAC Com Hot 24 VAC Common Com ...

Страница 8: ...olar detects the Dual Temp Weep configuration automatically when you install two Temperature Probes but configure Aux 1 for control by Time rather than by the attached sensor Zolar then automatically assigns the purpose of the second Temperature Probe to that of Dual Temp Weep 3 Zolar automatically detects the presence or absence of a Temperature Probe When a Temperature Probe is not installed for...

Страница 9: ...control by time of day then Zolar will use the second Sensor Input in the dual Temperature Probe configuration for the Weep Output Note If the Auxiliary Output is configured for control by time of day and a 2nd Temperature Probe is not connected Zolar will ignore the 2nd Sensor Input Ambient Light Probe Notes The Z440LP Light Probe consists of a light sensor encapsulated in a light diffusing high ...

Отзывы: