19
IDS 805 Installer Manual 700-266-02H Issued September 2009
The Engineer reset function determines whether the panel can be armed after an alarm condition has
been registered. This can be used to force the customer to have the system inspected in the event of an
alarm condition.
If the function is enabled:
If an alarm condition occurs and a valid user code is entered, thereby disarming the system, a
trouble condition will be indicated. Upon entering the Trouble mode (hold down
[7]
), the
indicator for zone 8 is on indicating that the installers code must be entered to clear this
condition before re-arming. To clear the engineer reset simply enter the program mode by
entering a valid
[INSTALLER CODE]
followed by
[*]
followed by
[#]
to exit the program
mode. The panel can now be armed.
If the function is disabled:
The panel can be rearmed normally after an alarm condition has been registered. No trouble
condition will be indicated.
LOCATION 13
Stay Arm Options
Value
Action
0 Default The Alarm Panel will automatically arm in the stay mode if the user arms and
does not use the Entry/Exit zone (i.e. violation of an Entry/Exit zone).
1
The Alarm Panel will arm in the away mode even if no violation of an Entry/Exit
zone occurs. The stay mode quick arm key (holding down
[5]
is also disabled.
2
The Alarm Panel will arm in the away mode even if no violation of an Entry/Exit
zone occurs, however the stay mode quick arm key remains active.
The stay mode allows the user access to certain pre-programmed "stay" zones while the panel is armed.
Zones that are programmed as stay zones (See Section 12 in the User Manual) will automatically be
bypassed when the panel is armed into the stay mode. The
[5]
key will arm the panel in stay mode with
no exit delay.
LOCATION 14
Silent Keypad Panic Options
Value
Action
0 Default
Disabled (audible panic)
1
Enabled (silent panic)
The value programmed into this location only affects the keypad panic.
LOCATION 15
Silent Alarm Options
Value
Action
0 Default
Disabled (audible alarm)
1
Enabled (silent alarm)
If a zone is programmed as a Silent Instant zone, an alarm condition as a result of a violation of this zone
would be silent regardless of the value programmed into this location.
Содержание 805
Страница 1: ...1 IDS 805 Installer Manual 700 266 02H Issued September 2009...
Страница 2: ...2 IDS 805 Installer Manual 700 266 02H Issued September 2009...
Страница 5: ...5 IDS 805 Installer Manual 700 266 02H Issued September 2009...
Страница 6: ...6 IDS 805 Installer Manual 700 266 02H Issued September 2009...
Страница 48: ...48 IDS 805 Installer Manual 700 266 02H Issued September 2009...