T
H E
P O W E R
F A M I L Y
(C) IDM ENERGIESYSTEME GMBH
Installation TERRA S/W
39
1
2
3
4
5
6
7
8
9
10
11
12
13
1
2
3
4
5
60
190
1 1/4”
connection pipes
to heat pump
on site!
manifold length L
connection set
PE-pipe Ø 25
Heat source
H
e
a
t sour
ce
5.3.4. Installation diagram
Notes
-
Only antifreeze approved by IDM-Energiesysteme
GmbH may be used.
-
Brine circuit lines must be provided with steam
diffusion-tight insulation in the event of the forma-
tion of condensation and the accumulation of ice
(e.g. Armafl ex).
-
Brine circuit pump and brine circuit expansion ves-
sel must be positioned on the heat pump inlet side
(warm side).
- The brine circuit expansion vessel must be con-
nected from the brine line upwards.
-
When fi lling the brine circuit with the antifreeze mix
the expansion vessel must be fi lled
Type TS
Unit
1/60
1/70
1/80
1/100
2/130
2/150
2/190
3/225
3/270
3/300
4/340
4/400
5/475
6/570
7/700
No. of boreholes
1
1
1
1
2
2
2
3
3
3
4
4
5
6
7
Total probe depth
m
60
70
80
100
130
150
190
225
270
300
340
400
475
570
700
Probe pipe
Ø
mm
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
Brine mix
l
105 120 140 175
225
260
325
350
460
510
580
680
810
970
1180
Probe pipe Ø
mm 2x32 2x32 2x32 2x32 2x32 2x32 2x32 2x32 2x32 2x32 2x32 2x32 2x32
2x32
2x32
Brine mix
l
135 155 175
220
285
325
410
485
580
645
730
860
1020 1220
1500
Connec
ti
on line Ø
mm
32
32
32
32
40
40
40
50
50
50
50
65
65
65
73
Recomm. circula
ti
on
pump
25/7 25/7 25/7 25/7 25/7 25/7 25/7 25-80 32-80 32-80 32-80 40/10 40/10 50/10 50/10
Technical Data