30
Table 3.
Recommended O-ring Lubricant
Application
Lubricant 1/
O-ring
Synthetic Multi-Purpose Clear O-ring Lubricant
(Synthetic NLGI Grade 2 Heavy Duty, Multi-Purpose)
Note 1
Or equivalent lubricant.
4.1.4
Thread Lock And Sealant Compounds
Loctite®
™ (or suitable equivalent/substitute thread locker, bonding compound, or sealant)
shall
be used when directed. Reference the procedures associated list of tools and/or consumables
for the specific thread locker/bonding or sealant required. Loctite®
™ (
242/243/270) and seal-
ant (580) was used during factory assembly for all fasteners/hardware and fittings requiring the
use of a thread lock, bonding, or sealant compound. Remnant compound ALWAYS causes false
torque reading when installing old and/or new fasteners/hardware. See paragraph 4.1.2 Rec-
ommended Cleaners, for thread lock or bonding compound cleaning information. The Loctite®
™
compounds listed in Table 4 may be used for thread lock or bonding compounds.
Table 4.
Recommended Thread Lock And Sealant Compounds
Thread Lock
Compounds
Used on:
(Description)
Sealant
Compounds
Used on:
(Description)
Loctite®
242/243
™
Mounting and Retaining Hardware (Me-
dium Strength, All-Purpose, Removable,
Thixotropic, Blue)
Loctite®
580™
Pipe Fittings
(Medium Strength, High
Temperature, Slow Cure,
White)
Loctite®
270™
Eductor Threads
(High Strength High Temperature, Slow
Cure, Green)
4.2.
Cleaning and Inspection Guidelines
Wherever a procedure calls for cleaning and inspection, these guidelines should be followed.
A.
Inspect all components for excessive or abnormal wear.
B.
Wherever a requirement for new parts is indicated, obtain new components from
Hale Products Inc.
C.
Wherever procedures call for removal of gaskets, gasket should be replaced.
Clean all gasket mating surfaces before installing new gaskets.
D.
Replace any hardware that shows signs of excessive wear, corrosion, or
bolts/screws that are torqued to greater than 100 ft-lb with new hardware.
4.2.1
Cleaning Required for Thread Lock Compounds
Always clean the threads of all bolts/fasteners/screws as remnant compound causes false
torque reading when installing existing hardware. Always use a clean out tap to clean old thread
lock from bolt/ fastener/screw holes to prevent remnant compound causing false torque reading
when installing old and/or new hardware.
To remove and clean factory installed thread lock compounds, follow the instruction provided in
the applicable Loctite®
™ Technical Data Sheet (See the Loctite
® web site [http://www.loc-
tite.com] or Henkel web site [https://www.henkel.com].)
Содержание HALE MIV 2.0
Страница 2: ......
Страница 8: ...vi THIS PAGE INTENTIONALLY BLANK...
Страница 14: ...6 THIS PAGE INTENTIONALLY BLANK...
Страница 32: ...24 HIS PAGE INTENTIONALLY BLANK...
Страница 35: ...27 THIS PAGE INTENTIONALLY BLANK...
Страница 36: ......
Страница 49: ...41 Figure 12 MIV Control Module...
Страница 50: ...42 THIS PAGE INTENTIONALLY BLANK...
Страница 51: ...43 5 PARTS LIST...
Страница 55: ...47 THIS PAGE INTENTIONALLY BLANK...
Страница 56: ...48 6 INSTALLATION DRAWING...
Страница 58: ......