3 Project Settings Dialog Box
4-32
WindO/I-NV4 User’s Manual
System Area 2
This area stores MICRO/I states and error information. These bits are 0 immediately after the power is turned on.
*1 HG5G/4G/3G/2G-V, HG4G/3G, HG2G-5F only
*2 USB flash drive inserted in USB1 for HG2J-7U, SD memory card for HG5G/4G/3G-V, HG4G/3G and HG2G-5F
*3 HG2G-5T, HG1G/1P only
*4 HG5G/4G/3G/2G-V, HG4G/3G, HG2G-5F/-5T, HG1G only
*5 HG2J-7U, HG5G/4G/3G/2G-V, HG4G/3G, HG2G-5F/-5T, HG1G only
*6 Only clock data is lost for HG2J-7U.
Address
number
Bit
Function
Description
+2
0 to 2
Reserved
3
Communication error
This bit changes to 1 when a communication error occurs in external
device communication. To clear this bit, write 1 to the Clear error bit
(System Area 1 address 1, bit 9).
4
Reserved
5
Processing error
This bit changes to 1 when executing the following arithmetic operations.
To clear this bit, write 1 to the Clear error bit (System Area 1 address
1, bit 9).
• There is data which cannot be handled with the specified data type;
BCD4(B), BCD8(EB), or Float32(E).
• A value is divided by 0.
• The setting of Origin, Minimum, or Maximum for the Bar Chart or Line
Chart are invalid, or the Minimum and Maximum are the same values.
• The setting of Minimum, Maximum, or ranges for the Meter are invalid,
or the Minimum and Maximum are the same values.
• There is invalid clock data which is used in Calendar parts.
6
Device range error
This bit changes to 1 when writing a value to a device address that falls
outside its range or when exceeding the restrictions on the number of
configured device addresses. To clear this bit, write 1 to the Clear error bit
(System Area 1 address 1, bit 9).
7
Clock IC error
This bit changes to 1 when the MICRO/I internal clock stops. To clear this
bit, write 1 to the Clear error bit (System Area 1 address 1, bit
9).
8
External memory device
(A:) access error
This bit changes to 1 when an error occurs when the external memory
device inserted in the MICRO/I is accessed. To clear this bit, write 1 to the
Clear error bit (System Area 1 address 1, bit 9).
9
Printer timeout error
This bit changes to 1 when a printing error occurs when data is output to
the printer connected to the MICRO/I. To clear this bit, write 1 to the
Clear error bit (System Area 1 address 1, bit 9).
10
Script error
This bit changes to 1 when an error occurs during script execution. Error
details are stored in HMI Special Data Registers LSD52 and LSD53. For
details, refer to Chapter 20 “1.4 Script Error” on page 20-4. To clear this
bit, write 1 to the Clear error bit (System Area 1 address 1, bit
9).
11
External memory device
(B:) access error
This bit changes to 1 when an error occurs when accessing an inserted
USB flash drive.
12
Replace battery error
This bit changes to 1 when it is time to replace the backup battery. To
clear this bit, write 1 to the Clear error bit (System Area 1 address
1, bit 9).
13
Replace battery error (low
battery)
This bit changes to 1 when the backup battery is low. To clear this bit,
write 1 to the Clear error bit (System Area 1 address 1, bit 9).
14
Backup data error
This bit changes to 1 when the data sampled by the log functions, the
clock data and values in the HMI Keep Registers and HMI Keep Relays
disappears
. To clear this bit, write 1 to the Clear error bit (System Area
1 address 1, bit 9).
15
Reserved
Содержание WindO/I-NV4
Страница 1: ...B 1701 16 User s Manual...
Страница 50: ...1 WindO I NV4 Specifications 2 18 WindO I NV4 User s Manual Baltic ANSI 1257 Cyrillic ANSI 1251...
Страница 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Страница 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Страница 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Страница 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Страница 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Страница 522: ...5 Key Button 8 102 WindO I NV4 User s Manual Password Input These keys switch the user on the Password Input Screen...
Страница 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Страница 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Страница 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Страница 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Страница 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Страница 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Страница 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Страница 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Страница 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Страница 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Страница 1694: ...5 HG1P 35 80 WindO I NV4 User s Manual 5 6 Dimensions Unit mm Cable Dimensions 191 169 56 70 6 51 55 7...
Страница 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...