1 Bit Devices
33-2
WindO/I-NV4 User’s Manual
■
HMI Special Relay (LSM)
A specific function is assigned for each of the 96 special internal relay (LSM0 to LSM95). The supported device
addresses vary based on the model.
Yes: Supported, No: Not supported, (blank): Reserved
*6 USB flash drive inserted in USB2 for HG2J-7U
*7 USB flash drive inserted in USB1 for HG2J-7U, SD memory card for HG5G/4G/3G/2G-V, HG4G/3G and HG2G-5F
Device
Address
Function/Part
HG2J
-7U
HG5G/
4G/3G/
2G-V
HG4G/
3G,
HG2G-
5F
HG2G
-5T,
HG1G
/1P
LSM0
Always set to 1.
Yes
Yes
Yes
Yes
LSM1
When the default screen is displayed after the power turned ON or when
the Base Screen swicthed, the value of this bit is 1 only on the second scan.
It also operates when switching text group or user account, or
resetting the display screen.
Yes
Yes
Yes
Yes
LSM2
When the default screen is displayed after the power turned ON or when
the Base Screen swicthed, the value of this bit is 1 only on the first scan.
It also operates when switching text group or user account, or
resetting the display screen.
Yes
Yes
Yes
Yes
LSM3
When the default screen is displayed after the power turned ON or when
the Base Screen swicthed, the value of this bit is 0 only on the first scan.
It also operates when switching text group or user account, or
resetting the display screen.
Yes
Yes
Yes
Yes
LSM4
Alternates between 0 and 1 with each scan.
Yes
Yes
Yes
Yes
LSM5
When Popup Screen is opened, the value of this bit is 1 only on the first scan.
Yes
Yes
Yes
Yes
LSM6
While touch panel is pressed, the value of this bit is 1.
Yes
Yes
Yes
Yes
LSM7
Alternates between 0 and 1 each time data is read (read scan) from all the
external device addresses being used by External Device Communication 1.
Yes
Yes
Yes
Yes
LSM8
When the power is turned ON, the value of this bit changes to 1.
When switching to another screen from the default screen or when
switching text group or user account, then the value changes to 0.
Yes
Yes
Yes
Yes
LSM9
When value changes from 0 to 1, the backup data stored in flash
memory is restored.
When it becomes 1 value does not become 0 until the Touch is reset
or 0 is written.
Yes
Yes
Yes
Yes
LSM10
When switched from 0 to 1, the current backlight setting and the data
for Keep Relays and Keep Register configured in the Data Storage
Area are transferred to the flash memory.
Once LSM10 switches to 1, it does not change to 0 until MICRO/I
recycles power or 0 is written to LSM10.
Yes
Yes
Yes
Yes
LSM11
When the default screen gets displayed after the power turned ON or
when the Base Screen gets switched, the values of all external device
addresses in use are read first. Then the bit changes from 0 to 1. The
bit remains 1 until the screen gets switched to another screen.
It also operates when switching text group or user account, or
resetting the display screen.
Yes
Yes
Yes
Yes
LSM12
When Popup Screen is closed, the value of this bit is 1 only on the
first scan.
Yes
Yes
Yes
Yes
LSM13
Value becomes 0 when Popup Screen is opened, and then changes
from 0 to 1 after the values of all external device addresses being
used by that Popup Screen are read.
Yes
Yes
Yes
Yes
LSM14 to 17 Reserved
LSM18
When value changes from 0 to 1, access to USB flash drive
is
stopped. The access state can be checked with the value of LSM19.
When it becomes 1 value does not become 0 until the MICRO/I is
reset or 0 is written.
Yes
Yes
Yes
Yes
LSM19
Bit is 1 during USB flash
access. When 0, the USB flash
removed.
Yes
Yes
Yes
Yes
LSM20
Access to the external memory device
stops when this bit is switched
from 0 to 1. The access state can be checked with the value of LSM21.
Yes
Yes
Yes
No
LSM21
Bit is 1 during external memory device
access. When 0, the external
memory device
can be removed.
Yes
Yes
Yes
No
Содержание WindO/I-NV4
Страница 1: ...B 1701 16 User s Manual...
Страница 50: ...1 WindO I NV4 Specifications 2 18 WindO I NV4 User s Manual Baltic ANSI 1257 Cyrillic ANSI 1251...
Страница 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Страница 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Страница 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Страница 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Страница 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Страница 522: ...5 Key Button 8 102 WindO I NV4 User s Manual Password Input These keys switch the user on the Password Input Screen...
Страница 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Страница 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Страница 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Страница 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Страница 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Страница 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Страница 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Страница 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Страница 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Страница 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Страница 1694: ...5 HG1P 35 80 WindO I NV4 User s Manual 5 6 Dimensions Unit mm Cable Dimensions 191 169 56 70 6 51 55 7...
Страница 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...