IDEC SmartRelay installation and wiring
29
IDEC SmartRelay Manual
2.3.2
Connecting IDEC SmartRelay inputs
Requirements
At the inputs you connect sensor elements such as: momen-
tary switches, switches, light barriers, daylight control
switches etc.
Sensor characteristics for IDEC SmartRelay
FL1D-H12RCE
FL1D-B12RCE
FL1B-M08B2R2
(1),(2)
(1) : 1.0 mA (Version 1 to 5 specifications)
(2) : 8 V DC (Version 1 to 5 specifications)
FL1D-H12SND
FL1B-M08B1S2
(3),(4),(5)
(3) : 1.0 mA (Version 1 to 4 specifications)
(4) : 8 V DC (Version 1 to 4 specifications)
(5) : 1.5 mA (Version 1 to 4 specifications)
For identifying the version, see page 4.
I1 ... I6
I7, I8
I1 ... I6
I7, I8
Signal status 0
< 5 VDC
< 5 VDC
< 5 VDC
< 5 VDC
Input current
< 0.05 mA
< 0.85 mA
< 0.05 mA
Signal status 1
> 8.5 V DC
> 12 V DC
> 12 V DC
Input current
> 1.5 mA
> 0.1 mA
> 2 mA
> 0.15 mA
FL1D-
H12RCA/
FL1D-
B12RCA (AC)
FL1B-M08
D2R2 (AC)
FL1D-
H12RCA/
FL1D-
B12RCA (DC)
FL1B-M08
D2R2 (DC)
FL1D-
H12RCC/
FL1D-
B12RCC (AC)
FL1B-M08
C2R2 (AC)
FL1D-
H12RCC/
FL1D-
B12RCC (DC)
FL1B-M08
C2R2 (DC)
Signal status 0
< 5 V AC
< 5 V DC
< 40 V AC
< 30 V DC
Input current
< 1.0 mA
< 1.0 mA
< 0.03 mA
< 0.03 mA
Signal status 1
> 12 V AC
> 12 V DC
> 79 V AC
> 79 V DC
Input current
> 2.5 mA
> 2.5 mA
> 0.08 mA
> 0.08 mA
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com