![IDEC SmartAXIS Touch FT1A Series Скачать руководство пользователя страница 621](http://html.mh-extra.com/html/idec/smartaxis-touch-ft1a-series/smartaxis-touch-ft1a-series_user-manual_617387621.webp)
SmartAXIS Touch User’s Manual
11-5
1 Bit Write Command
11
Commands
■
Destination Device
Specify the destination bit device.
Click
to display the Device Address Settings dialog box. For the device address configuration procedure, refer to
Chapter 2 “5.1 Device Address Settings” on page 2-62.
■
Write
Specify the number of bit devices (1 to 64) at the destination.
This setting is enabled only if
Action Mode
is set to
Set
or
Reset
.
Example: This fills a contiguous block of bit devices with the same value.
If the bit of the word device is specified, the same value is written to same bit of contiguous word devices.
■
Source Data
Specifies the device where the data to be written is stored.
This setting is enabled only if
Action Mode
is set to
Move
.
Example: This button writes the values in a contiguous block of bit devices to a contiguous block of devices at the
destination.
*1 Advanced mode only
Toggle:
Toggles the value of the specified bit device when the trigger condition is satisfied.
If the value of the bit device is 0 it changes to 1, and vice versa.
Move:
This function writes the value in the source bit device to the value in the destination bit device
when the trigger condition is satisfied.
State of condition
Action
Toggle
Toggle
Condition
Condition
Condition
Condition
Satisfied
Satisfied
Satisfied
Not satisfied
Not satisfied
Not satisfied
Satisfied
Satisfied
Satisfied
Not satisfied
Not satisfied
Not satisfied
State of condition
Action
Move
Move
Condition
Condition
Condition
Condition
Satisfied
Satisfied
Satisfied
Not satisfied
Not satisfied
Not satisfied
Satisfied
Satisfied
Satisfied
Not satisfied
Not satisfied
Not satisfied
1
M0
1
M1
1
M2
1
M3
1
M4
Action Mode: Set
Write: 5
Destination Device: M0
Condition
Satisfied
Satisfied
Satisfied
Condition
bit
bit
15
0
Satisfied
Satisfied
Satisfied
1
D0
D1
D2
D3
D4
1
1
1
1
Action Mode: Set
Write: 5
Destination Device: D0-15
Device:
Specify the source bit device.
Click
to display the Device Address Settings dialog box. For the device address configuration
procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-62.
Transfer:
Specify the number of bit devices (1 to 64) to move.
1
LM0
0
LM1
0
LM2
1
LM3
Device: LM0
Transfer: 4
Destination Device: M0
1
M0
0
M1
0
M2
1
M3
Condition
Satisfied
Satisfied
Satisfied
Содержание SmartAXIS Touch FT1A Series
Страница 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Страница 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Страница 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Страница 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Страница 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Страница 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Страница 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Страница 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Страница 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Страница 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Страница 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Страница 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Страница 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Страница 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Страница 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Страница 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...