6 Alarm List Display
9-88
SmartAXIS Touch User’s Manual
Individual Settings Dialog Box
The Individual Settings dialog box is used to configure the conditions to display the messages.
■
Trigger Device
Specifies the word device to use as the condition to display messages. The bit of the word device corresponds to the
message numbers.
Example: When the number of blocks is 1 and D0 is specified as the trigger device
Message number 1-0 device bit is D0-0, message number 1-1 device bit is D0-1, up to message number
1-15 device bit which is D0-15.
Click
to display the Device Address Settings dialog box. For the device address configuration procedure, refer to
Chapter 2 “5.1 Device Address Settings” on page 2-62.
When
Serial
is selected for
Device Setting Method
on the
List
tab, the trigger devices for block numbers after the
block number being registered or edited are automatically changed with the configured trigger device as the starting
address.
■
(Settings)
Insert:
Inserts the block settings in the position selected on the list.
Select the block number at the position to insert the settings in the list, and then click this button to
display the Individual Settings dialog box. For details, refer to “Individual Settings Dialog Box” on page
9-88.
The settings at the insertion point shift down one line. Settings cannot be inserted if all block
numbers are configured.
Delete:
Deletes the registered settings from the list.
Select a block number on the list, and then click this button to delete the selected settings from the list.
(Settings)
D0-0
D0-1
D0-2
D0-14
D0-15
1-0
1-1
1-2
1-14
1-15
Block 1
16 channels
Msg. No.
Device bit
Msg. No.:
Displayed as (Block No.)-(Message No.).
Alarm function:
Selects whether or not to use the alarm function. Double clicking the cell switches between
Enable
and
Disable
.
Enable:
Monitors the state of the device bit configured for the channel and displays the message.
Disable: The device bit is not monitored and the message is not displayed.
NO/NC:
Selects the alarm detection condition. Double clicking the cell switches between
NO
and
NC
.
NO:
Displays the message when the monitored bit changes from 0 to 1.
NC:
Displays the message when the monitored bit changes from 1 to 0.
Text ID:
Shows the Text Manager ID number (1 to 32000) to use for the message.
The text ID is sequentially configured starting with the text ID configured by
Start Text ID
on
the
List
tab.
Text:
Shows the text for the specified text ID.
Only shows the first line of text when the text registered to the text ID has multiple lines.
Содержание SmartAXIS Touch FT1A Series
Страница 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Страница 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Страница 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Страница 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Страница 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Страница 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Страница 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Страница 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Страница 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Страница 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Страница 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Страница 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Страница 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Страница 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Страница 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Страница 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...