FT1A S
MART
A
XIS
U
SER
’
S
M
ANUAL
FT9Y-B1382
6-5
6: M
OVE
I
NSTRUCTIONS
MOVN (Move Not)
Applicable CPU Modules
Valid Devices
For the valid device address range, see pages 6-1 and 6-2
(Basic Vol.).
Internal relays M0 through M1277 can be designated as D1. Special internal relays cannot be designated as D1.
When T (timer) or C (counter) is used as S1, the timer/counter current value (TC or CC) is read out. When T (timer) or C (counter) is used as D1,
the data is written in as a preset value (TP or CP) which can be 0 through 65535.
Valid Data Types
Examples: MOVN
S1 NOT
D1
When input is on, 16- or 32-bit data from device designated by S1 is inverted bit by bit
and moved to device designated by D1.
REP
**
S1(R)
*****
D1(R)
*****
MOVN(*)
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
First device address to move
X
X
X
X
X
X
X
X
1-99
D1 (Destination 1)
First device address to move to
—
X
X
X
X
X
—
1-99
W (word)
X
When a bit device such as I (input), Q (output), M (internal relay), or R (shift register) is designated as the source
or destination, 16 points (word or integer data type) or 32 points (double-word or long data type) are used. When
repeat is designated for a bit device, the quantity of device bits increases in 16- or 32-point increments.
When a word device such as T (timer), C (counter), or D (data register) is designated as the source or destination, 1
point (word or integer data type) or 2 points (double-word or long data type) are used. When repeat is designated for
a word device, the quantity of device words increases in 1- or 2-point increments.
I (integer)
X
D (double word)
X
L (long)
X
F (float)
—
M10 NOT
M50
When input I0 is on, the 16 internal relays starting with M10 designated by source device
S1 are inverted bit by bit and moved to 16 internal relays starting with M50 designated
by destination device D1.
The ON/OFF statuses of the 16 internal relays M10 through M17
and M20 through M27 are inverted and moved to 16 internal
relays M50 through M57 and M60 through M67. M50 is the LSB
(least significant bit), and M67 is the MSB (most significant bit).
I0
REP
S1 –
M10
D1 –
M50
MOVN(W)
M10 through M17, M20 through M27 NOT
M50 through M57, M60 through M67
Before inversion
0
1
0
0
1
0
0
0
0
1
0
0
1
0
1
1
MSB
LSB
S1
After inversion
1
0
1
1
0
1
1
1
1
0
1
1
0
1
0
0
MSB
LSB
D1
(M27-M10):
(M67-M50):
810 NOT
D2
When input I1 is on, decimal constant 810 designated by source device S1 is converted
into 16-bit binary data, and the ON/OFF statuses of the 16 bits are inverted and moved
to data register D2 designated by destination device D1.
I1
REP
S1 –
810
D1 –
D2
MOVN(W)
D1
D0
64725
D2
810
Before inversion (810):
0
0
1
0
0
0
0
1
0
1
1
0
0
0
1
0
MSB
LSB
S1
After inversion (64725):
1
1
0
1
1
1
1
0
1
0
0
1
1
1
0
1
MSB
LSB
D1
D30 NOT
D20
When input I2 is on, the data in data register D30
designated by S1 is inverted bit by bit and moved to data
register D20 designated by D1.
I2
REP
S1 –
D30
D1 –
D20
MOVN(W)
64605
D20
930
D30
Содержание microsmart pentra
Страница 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Страница 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...