WindO/I-NV4 User’s Manual
13-23
3 Alarm Log Settings Dialog Box
13
Alarm Log Function
■
Real Time
Select this check box to output data to the external memory device
in real time.
With real time output, data is saved to the external memory device
in three minute intervals after the MICRO/I
starts running. If the accumulated data reaches 819th item, then the data is forcibly saved to the external memory
device
. When there is already data with the same file name on the external memory device
, data is appended to
that file. If there was no update to the data during the three minutes, it is not output.
Data is appended to the file until the size of the file reaches the restriction size (256 MB), so the maximum amount of
output data varies based on the settings for the output channel such as the amount of data, the data size, and the labels.
If the interval to update the Alarm Log is shorter than real time output (the interval for writing to the external memory
device), that Alarm Log is recorded up to the 1023rd item, and then afterwards, old data is discarded in order and
replaced with new data.
*1 SD memory card for HG5G/4G/3G/2G-V, HG4G/3G and HG2G-5F, USB flash drive for HG2G-5T and HG1G/1P
MICRO/I
Alarm Log data (CSV)
Alarm Log data
Time
State
Ch.No.
Message
12/01/2011 12:00:05
Occurred 1-1 Voltage
drop
12/01/2011 12:01:09
Occurred 1-2 Temperature abnormal
12/01/2011 12:01:10
Recovered 1-1 Voltage
drop
12/01/2011 12:03:30
Confirmed 1-1 Voltage
drop
12/01/2011 12:03:09
Occurred 1-3 Overcurrent
12/01/2011 12:04:33
Recovered 1-2 Voltage
drop
12/01/2011 12:05:15
Confirmed 1-2 Voltage
drop
12/01/2011 12:08:41
Recovered 1-3 Overcurrent
Data to be output
3 minutes after
operation starts
Data to be output
3 minutes after that
Data to be output after
another 3 minutes
3 minute interval
after operation starts
Output to
External memory device
External Memory Device
USB flash drive
SD memory card
Real time output stops when the file size of the Alarm Log data exceeds 256 MB or when there is
insufficient space on the external memory device. The error information is stored in the following HMI
Special Data Registers. For details about the error information, refer to Chapter 33 “HMI Special Data
Register (LSD)” on page 33-7.
SD memory card:
USB flash drive:
LSD42
LSD33
• When the value of the following HMI Special Internal Relays changes from 0 to 1, the data at that time is
first output in real time to the external memory device, and then access to the external memory device is
stopped. For details, refer to Chapter 33 “HMI Special Relay (LSM)” on page 33-2.
SD memory card:
USB flash drive:
LSD20
LSD18
• The amount of free space on the external memory device is saved to the following HMI Special Data
Registers. For details about the free space on the External Memory Devices, refer to Chapter 33 “HMI
Special Data Register (LSD)” on page 33-7.
SD memory card:
USB flash drive:
LSD43, 44
LSD34, 35
Trigger Condition: Select the check boxes for the items that will trigger the output of Alarm Log data to the external memory
device.
Occurrence:
Alarm Log data is output to the external memory device when an alarm has
occurred.
Recovery:
Alarm Log data is output to the external memory device when the alarm is
recovered from.
Confirmation: Alarm Log data is output to the external memory device when the key button
CHECK
was
pressed.
Month/day/year hour:minute:second is output for the trigger condition occurrence time, recovery time, and
confirmation time.
Содержание MICRO/I HG4G-CJT22 F-B Series
Страница 1: ...B 1701 11 User s Manual ...
Страница 26: ...Preface 25 WindO I NV4 User s Manual ...
Страница 50: ...1 WindO I NV4 Specifications 2 18 WindO I NV4 User s Manual Baltic Font ANSI 1257 Cyrillic Font ANSI 1251 ...
Страница 106: ...5 WindO I NV4 Common Operations and Settings 2 74 WindO I NV4 User s Manual ...
Страница 254: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual ...
Страница 362: ...5 Screen Restrictions 5 28 WindO I NV4 User s Manual ...
Страница 402: ...3 Text 7 30 WindO I NV4 User s Manual ...
Страница 574: ...9 Potentiometer 8 172 WindO I NV4 User s Manual ...
Страница 1052: ...4 Using the Data 15 22 WindO I NV4 User s Manual ...
Страница 1170: ...6 Important Notes 20 60 WindO I NV4 User s Manual ...
Страница 1200: ...5 Restrictions 22 18 WindO I NV4 User s Manual ...
Страница 1260: ...5 Editing User Accounts on the MICRO I 23 60 WindO I NV4 User s Manual ...
Страница 1286: ...4 Clear 24 26 WindO I NV4 User s Manual 4 Click Yes 5 Click Close This concludes clearing data ...
Страница 1288: ...4 Clear 24 28 WindO I NV4 User s Manual 6 Click Yes 7 Click Close This concludes clearing data on the external memory device ...
Страница 1322: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual ...
Страница 1414: ...4 E mail Function 28 66 WindO I NV4 User s Manual ...
Страница 1554: ...3 Settings 34 14 WindO I NV4 User s Manual ...
Страница 1642: ...2 Handling Problems 36 6 WindO I NV4 User s Manual ...
Страница 1652: ...5 Text Alignment A 10 WindO I NV4 User s Manual ...
Страница 1664: ...Index 12 WindO I NV4 User s Manual ...