Function Area Setting for L
ON
W
ORKS
Node
The quantity of transmit/receive data for L
ON
W
ORKS
network communication is specified using the Function Area Setting
in
WindLDR
. The
OpenNet Controller
CPU module recognizes all functional modules, such as OpenNet interface modules
and analog I/O modules, automatically at power-up and exchanges data with L
ON
W
ORKS
nodes through the link registers
allocated to each node.
Since these settings relate to the user program, the user program must be downloaded to the
OpenNet Controller
after
changing any of these settings.
Programming WindLDR
1.
From the
WindLDR
menu bar, select Configure > Function Area Settings. The Function Area Setting dialog box
appears.
2.
Select the Open Bus tab.
3.
Select transmit and receive data bytes for module position 1 through 7 where the L
ON
W
ORKS
interface module is
mounted.
4.
Click the OK button and download the user program to the
OpenNet Controller
.
Configure Communication
Master Module Check Box
Check this box only when
the remote I/O master
module is used.
Quantity of Nodes Connected
When using the remote I/O mas-
ter module, specify the quantity
of nodes from 1 through 32.
Slave Station
Transmit/Receive
Data Quantity (Bytes)
When using OpenNet inter-
face modules for DeviceNet,
INTERBUS, or L
ON
W
ORKS
,
specify the data bytes to
communicate through each
OpenNet inter face module.
Transmit/Receive Bytes 0 to 8
(default: 8 bytes)
This value determines the data
quantity 0 through 8 bytes (64
bits) to communicate with the
network.
For the example on the next
page, select 8 transmit bytes and
4 receive bytes for Module 1.