M8000 Start Control
M8000 is used to control the operation of the CPU. The CPU stops operation when M8000 is turned off while the CPU is running.
M8000 can be turned on or off using the WindLDR Online menu. When a stop or reset input is designated, M8000 must remain on
to control the CPU operation using the stop or reset input.
M8000 maintains its status when the CPU is powered down. When the data to be maintained during power failure is broken after
the CPU has been off for a period longer than the battery backup duration, the CPU restarts operation or not as selected in
Configuration
>
Run/Stop Control
>
Run/Stop Selection at Memory Backup Error
. For details on SmartAXIS Pro/Lite
start control, see "Run/Stop Selection at Memory Backup Error" on page 5-5.
M8001 1-sec Clock Reset
While M8001 is on, M8121 (1-sec clock) is turned off.
M8002 All Outputs OFF
When M8002 is turned on, all outputs and remote outputs go off until M8002 is turned off. Self-maintained circuits using outputs
also go off and are not restored when M8002 is turned off.
M8003 Carry (Cy) and Borrow (Bw) [Ladder program only]
When a carry or borrow results from executing an addition or subtraction instruction, M8003 turns on. M8003 is also used for the
bit shift and rotate instructions. For the causes of carry (CY) and borrow (BW), when ladder program is selected as the
programming language, see Chapter 4 "Instructions Reference" – "Carry and Borrow" in the "SmartAXIS Ladder Programming
Manual".
M8130
Disconnect User
Communication Connection
Connection 1
Maintained
Cleared
Read/Write
X
―
M8131
Connection 2
Maintained
Cleared
Read/Write
X
―
M8132
Connection 3
Maintained
Cleared
Read/Write
X
―
M8133-
M8143
— Reserved —
―
―
―
―
―
M8144
Timer Interrupt Status (ON: Allowed, OFF: Prohibited)
Cleared
Cleared
Read
X
―
M8145-
M8147
— Reserved —
―
―
―
―
―
M8150
Comparison Result 1
Maintained
Cleared
Read
X
―
M8151
Comparison Result 2
Maintained
Cleared
Read
X
―
M8152
Comparison Result 3
Maintained
Cleared
Read
X
―
M8153
— Reserved —
―
―
―
―
M8154
Data Register ROM Backup
Write
Operating
Cleared
Read/Write
X
X
M8155
Read
Operating
Cleared
Read/Write
X
X
M8156-
M8157
— Reserved —
―
―
―
―
―
M8160
Key Input Status
ESC Key + Up Key
Cleared
Cleared
Read
X
X
M8161
ESC Key + Down Key
Cleared
Cleared
Read
X
X
M8162
ESC Key + Left Key
Cleared
Cleared
Read
X
X
M8163
ESC Key +Right Key
Cleared
Cleared
Read
X
X
M8164
M8165
— Reserved —
―
―
―
―
―
M8166
High-speed Counter (Group5/I6)
Comparison Output Reset
Cleared
Cleared
Read/Write
X
M8167
Gate Input
Maintained
Cleared
Read/Write
X
M8170
Reset Input
Maintained
Cleared
Read/Write
X
M8171
Comparison ON Status
Maintained
Cleared
Read
X
X
M8172
Overflow
Maintained
Cleared
Read
X
X
M8173
High-speed Counter (Group 6/I7)
Comparison Output Reset
Cleared
Cleared
Read/Write
X
M8174
Gate Input
Maintained
Cleared
Read/Write
X
M8175
Reset Input
Maintained
Cleared
Read/Write
X
M8176
Comparison ON Status
Maintained
Cleared
Read
X
X
M8177
Overflow
Maintained
Cleared
Read
X
X
Device
Address
Description
CPU
Stopped
Power
OFF
Read/
Write
Ladder
FBD
Содержание FT1A-B12RA
Страница 1: ...FT9Y B1378 5 ...
Страница 2: ......
Страница 208: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...
Страница 226: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...
Страница 340: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...
Страница 384: ...APPENDIX A 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 European Font ISO 8859 1 Cyrillic Font ANSI 1251 ...
Страница 385: ...SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 A 19 APPENDIX Japanese Font JIS X0201 ...
Страница 386: ...APPENDIX A 20 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...