Data Register Allocation - Blocks 2, 3 Basic Parameters (SHOT Action)
Block 2 (CH0) and block 3 (CH1) parameters are shown in the table below. The parameters of block 2 and 3
can be changed while the control of the PID module is enabled.
Offset from the
Control
Register
Parameter
Description
R/W
CH0
CH1
+26
+103 Proportional Term
Proportional band:
When input range unit is Celsius:
0 to 10000°C
(Range with a decimal point: 0.0 to 1000.0°C)
When input range unit is Fahrenheit:
0 to 10000°F
(Range with a decimal point: 0.0 to 1000.0°F)
When input is voltage or current input:
0.0 to 1000.0%
Proportional gain:
0.00 to 100.00%
R/W
+27
+104 Integral Time
0 to 10000 sec
R/W
+28
+105 Derivative Time
0 to 10000 sec
R/W
+29
+106 ARW (Anti-Reset Windup)
0 to 100%
R/W
+30
+107 Control Period
1 to 120 sec
R/W
+31
+108 Reset
When input range unit is Celsius:
-100.0 to 100.0 °C
When input range unit is Fahrenheit:
-100.0 to 100.0 °F
When input is voltage or current input:
-1000 to 1000
R/W
+32
+109
Output Manipulated Variable
Rate-of-Change
0 to 100%/sec
R/W
+33
+110
Set Point (SP) Rise Rate
When input range unit is Celsius:
0 to 10000°C/min
(Range with a decimal point: 0.0 to 1000.0°C/min)
When input range unit is Fahrenheit:
0 to 10000°F/min
(Range with a decimal point: 0.0 to 1000.0°F/min)
When input is voltage or current input:
0 to 10000/min
R/W
+34
+111
Set Point (SP) Fall Rate
When input range unit is Celsius:
0 to 10000°C/min
(Range with a decimal point: 0.0 to 1000.0°C/min)
When input range unit is Fahrenheit:
0 to 10000°F/min
(Range with a decimal point: 0.0 to 1000.0°F/min)
When input is voltage or current input:
0 to 10000/min
R/W
+35
+112
Loop Break Alarm (LA) Time 0 to 200 minutes
R/W
+36
+113
Loop Break Alarm (LA) Span
When input range unit is Celsius:
0 to 150 °C
(Range with a decimal point: 0.0 to 150.0°C)
When input range unit is Fahrenheit:
0 to 150 °F
(Range with a decimal point: 0.0 to 150.0°F)
When input is voltage or current input:
0 to 1500
R/W
+37
+114
Alarm 1 Value
See 5-18 for the valid range of alarm 1 to alarm 8 values.
R/W
+38
+115
Alarm 2 Value
R/W
+39
+116
Alarm 3 Value
R/W
+40
+117
Alarm 4 Value
R/W
+41
+118
Alarm 5 Value
R/W
+42
+119
Alarm 6 Value
R/W
+43
+120 Alarm 7 Value
R/W
+44
+121 Alarm 8 Value
R/W
+45
+122 Reserved
R/W