4. Output specifications

(1) When wiring to the non-intrinsically safe circuit side, connect to 

terminals A and C. The output circuit is not equipped with short-
circuit protection. If required, provide a protection in the external 
circuit.

(2) Some types of loads generate reverse emf or cause a large inrush 

current, resulting in a shorter operation life of output relay contacts. 
The operation life of contacts can be extended by preventing the 
reverse emf using a diode, RC, or varistor, or by suppressing the 
inrush current using a resistor or RL. Contacts are made of gold-clad 
silver. When using at a small current  and a low voltage(reference 
value: 0.1 mA, 0.1V), test the contact on the actual circuit before 
use.

(3) Transistor  output 

When connecting a small load, the load may not turn off because of 
a leakage current, even though the transistor output is turned off. If 
this is the case, connect a resistor in parallel with the load to bypass 
the leakage current.  
When an excessively high voltage or a reverse voltage is applied to 
the output terminals, the clamping circuit or output transistor may be 
damaged. 
When driving an inductive load, be sure to connect a diode across 
the load to absorb reverse emf. 

Example of an overvoltage absorption circuit

Load

(An)

(Cn)

: Surge absorber

5. Wiring for intrinsic safety

(1)  The voltage applied on the general circuit connected to the non-

intrinsically safe circuit terminals of the product must be 250V 
AC, 50/60Hz, or 250V DC at the maximum under any conditions, 
including the voltage of the input power and the internal circuit.

(2)  When wiring, take into consideration the prevention of 

electromagnetic and electrostatic charges on intrinsically safe 
circuits. Also, prevent intrinsically safe circuits from contacting with 
other circuits. The intrinsically safe circuits must be separated from 
non-intrinsically safe circuits.

(3)  Enclose intrinsically safe circuits in a metallic tube or duct, or 

separate the intrinsically safe circuits referring to the table below. 

Reference:  Cables with a magnetic shield, such as a metallic sheath, prevent 

electromagnetic induction and electrostatic induction, however, a 
non-magnetic shield cannot prevent electromagnetic induction.

Finely twisted pair cables prevent electromagnetic induction. 
Twisted pair cables with shields prevent electrostatic induction.

(4)  When identifying intrinsically safe circuits by color, use light blue 

terminal blocks and cables. 

Minimum parallel distance between the intrinsically safe circuit 
and other circuits (mm)

Voltage and current of 

other circuits

Over 100A

100A 

maximum

50A 

maximum

10A 

maximum

Over 440V

2000

2000

2000

2000

440V maximum

2000

600

600

600

220V maximum

2000

600

600

500

110V maximum

2000

600

500

300

60V maximum

2000

500

300

150

(5)  Make sure that the power of the relay barrier and contact part are 

turned off before inspection or replacement.

(6)  Connect one set of sensors per barrier channel.
(7)  When wiring the intrinsically safe circuit, determine the distance to 

satisfy the wiring parameters shown below.

(a) Wiring inductance: Lc≤0.453mH-Li
(b) Wiring capacitance: Cc≤5.8μF-Ci
(c)  Allowable wiring distance is the smallest value of those 

calculated from the capacitance, inductance, and resistance 
below.

Lc/L 

Cc/C 

(6.4V-Vmin.)/(16mA×2R)

L [mH/km]:Inductance of cable per km
C [nF/km]:Capacitance of cable per km
R [Ω/km]: Resistance of cable per km

Example: Vmin.=6.0V, Li=10μH, Ci=4.5μF, R=40Ω/km,

When L=1mH/km and C=0.2μF/km,
the possible sensor wiring distances from equations 

and 

Lc/L=443m
Cc/C=6.5km
(6.4V-6.0V)/(16mA×2×40)=312m
Therefore, the wiring distance is less than 312m.

(8)  Compatible wire size 

0.5 to 2.1mm

(AWG20 to 14)

Instructions

Be sure to read the instruction manual carefully before performing installation, wiring, or maintenance work.

For details on mounting, wiring, and maintenance, see the instruction manual from the below URL.
URL : https://product.idec.com/?product=EB3S-N

5

 EB3S Sensor Barrier (Intrinsically 

Safe

 Explosion-Proof)