IDEAL Vanguard L 1100 Скачать руководство пользователя страница 2

2

Vanguard L  - 

Installation & Servicing 

GENERAL

Note

.

Fuel rates and flue gas data relate to maximum output ratings.  

Gas firing data relates to the use of NATURAL GAS ONLY.  
Details for the use of LPG are available on request from Ideal.
Natural gas consumption is calculated using a calorific value of 

38.7MJ/m

3

 (1038Btu/ft

3

) gross or 34.9MJ/m

3

 (935Btu/ft

3

) nett at 

15ºC and 1013.25mbar.

Table 1 Performance Data

HEALTH & SAfETy DocumENT No. 635

The electricity at work regulations, 1989

.  The manufacturer's 

notes must NOT be taken, in any way, as overriding statutory 

obligations.

ImPoRTANT

. These appliances are CE certified for safety 

and performance.  It is, therefore, important that no external 

control devices, e.g. flue dampers, economisers etc., are 

directly connected to these appliances unless covered by 

these Installation and Servicing Instructions or as otherwise 

recommended by 

Ideal 

in writing.  If in doubt please enquire.

Any direct connection of a control device not approved by 

Ideal 

could invalidate the certification and the normal appliance 

warranty.  It could also infringe the Gas Safety Regulations and 

the above regulations.

Boiler 

Size 

 170 240 290 340 420 510  630  760 870  970 1100 1320 1570 1850 2200 2650 3000 3500

Maximum 

Heat 

Output 

kW 170 240 290 340 420 510  630  760 870  970 1100 1320 1570 1850 2200 2650 3000 3500

 Btu/hx10

3

  580  819  990 1160 1433 1740  2150  2593 2969  3301 3753 4504  5357  6312  7507  9042 10236 11942

Minimum 

Heat 

Output 

kW 130 180 220 255 315 385  480  580 660  750 860 1000 1200 1400 1700 2000 2300 2700

 Btu/hx10

3

 444  614  751 870 1075 1314 1638 1980 2252 2559 2934 3412 4095 4777 5800 6824 7848 9212

Hydraulic resistance 11K 

mbar 27.5 60.4 38.4 51.2 31.1 45.8  69.5  47.6 60.4  75.0 54.9 64.1  60.4  82.4  62.2  87.9  113.5 153.7

 

in 

wg 11.0 24.2 15.4 20.5 12.4 18.3  27.8  19.0 24.2  30.0 22.0 25.6  24.2  32.9  24.9  35.1  45.4  61.5

Hydraulic resistance 20K 

mbar 8.3 18.3 11.6 15.5 9.4 13.8 21.0 14.4 18.3 22.7 16.6 19.4 18.3 24.9 18.8 26.6 34.3 46.5

 

in 

wg 3.3 7.3 4.7 6.2 3.8 5.5  8.4  5.8 7.3  9.1 6.6 7.8  7.3 10.0 7.5 10.6 13.7 18.6

Combustion 

chamber 

mm 

w.g. 15 28 25 34 29 43  55  51 57  49 52 67  60  73  65  76  60  74

resistance (at zero draught)

 

in 

w.g. 0.59 1.10 0.98 1.34 1.14 1.69  2.17  2.01 2.24  1.93 2.05 2.64  2.36  2.87  2.56  2.99  2.36  2.91

Flow connection 

(T1)       DN PN16  65 

65 

80 

80  100  100  100 

125  125 

125  150  150 

175  175  200  200 

200  200

Return connection 

(T2)       DN PN16  65 

65 

80 

80  100  100  100 

125  125 

125  150  150 

175  175  200  200 

200  200

Max. 

operating 

pressure 

bar 

6 6 6 6 6 6  6  6 6  6 6 6  6  6  6  6  6  6

Max. boiler therm. setting 

ºC 60-90 60-90 60-90 60-90 60-90 60-90  60-90  60-90 60-90  60-90 60-90 60-90  60-90  60-90  60-90  60-90  60-90  60-90

Safety thermostat setting 

ºC 100 100 100 100 100 100  100  100 100  100 100 100  100  100  100  100  100  100

High-low setting 

ºC 54-84 54-84 54-84 54-84 54-84 54-84  54-84  54-84 54-84  54-84 54-84 54-84  54-84  54-84  54-84  54-84  54-84  54-84

Min. draught at smokehood

 

mbar 0.0 0.0 0.0 0.0 0.0 0.0  0.0  0.0 0.0  0.0 0.0 0.0  0.0  0.0  0.0  0.0  0.0  0.0

outlet 

(for 

max. 

output) 

in 

w.g. 0.0 0.0 0.0 0.0 0.0 0.0  0.0  0.0 0.0  0.0 0.0 0.0  0.0  0.0  0.0  0.0  0.0  0.0

Safety valve & expansion

  (T3)  BSP/DN PN6  1

1

/

2

"

 

1

1

/

2

"

 

2" 2" 2"  2"  2"  65 65  65 80 80 100 100 125 125 125 125

Drain 

(T4)                  in  3/4 

3/4 

3/4  3/4  3/4 

3/4 

3/4 

1

1

/

1

1

/

1

1

/

1

1

/

1

1

/

1

1

/

1

1

/

1

1

/

1

1

/

1

1

/

1

1

/

2

Flue outlet 

(T5)               mm  200  200  250  250  250  250  300 

350  350 

350  400  400 

450  450  520  520 

570  620

 

                  in  7.8 

7.8 

9.8  9.8  9.8 

9.8  11.8  13.8  13.8  13.8  15.7  15.7  17.7  17.7  20.5  20.5  22.4  24.4

Boiler 

water 

content 

l 190 251 264 298 398 462  565  671 753  836 1040 1242 1418 1617 2086 2324 2667 4142

 

gal  41.8  55.2  58.1  65.6  87.5  101.6  124.3  147.6 165.6  183.9 228.8 273.2  311.9  355.7  458.9  511.2  586.7  911.1

Boiler DRY weight less 

kg  435  510  588  629  796  919  1049  1341  1447  1553  1821  2030  2780  3280  4145  4465  5110  6700

burner unit 

lb  959  1124 1296 1387 1755 2026  2313  2956 3190  3424 4015 4475  6129  7231  9138  9844  11266 14771

Boiler 

Size 

 170 240 290 340 420 510  630 760  870  970 1100 1320 1570 1850 2200 2650 3000 3500

Maximum 

oil 

rate 

l/h 19.1 27.0 32.5 38.1 47.1 57.2  70.8 85.2  97.4 108.6 123.2 147.9 176.0 207.4 247.1 297.3 336.6 393.1

 

gal/h 4.2  5.9  7.2 8.4 10.4 12.6 15.6 18.7 21.4 23.9 27.1 32.5 38.7 45.6 54.4 65.4 74.0 86.5

Maximum flue  

m

3

/sec 0.10 0.14 0.17 0.20 0.25 0.31  0.37 0.44  0.52  0.56 0.64 0.76  0.91  1.07  1.26  1.52  1.72  1.99

gas volume 

ft

3

/min 209 299 356 417 523 648  775 932  1102 1189 1348 1620 1926 2255 2670 3213 3638 4221 

Flue Gas CO

at 

195ºC 

% 13.0 12.8 13.0 13.0 12.8 12.5  13.0 13.0  12.5  13.0 13.0 13.0  13.0  13.1  13.2  13.2  13.2  13.3

Table 2 oil firing Data

Boiler 

Size 

 170 240 290 340 420 510 630  760 870  970 1100 1320 1570 1850 2200 2650 3000 3500

Maximum Gas Rate 

m

3

/h 19.1 26.9 32.4 38.0 47.0 57.0 70.5  84.9 97.1 108.3 122.8 147.5 175.4 206.7 246.3 296.4 335.6 391.9

Gross ft

3

/h 

673.2  949.4  1144.7 1340.6 1657.9  2013.1 2489.5  2996.7 3426.7  3820.6 4332.6  5204.8 6190.6  7294.6  8693.5 10460.4 11841.9 13830.5

Maximum flue  

m

3

/sec 0.10 0.14 0.17 0.19 0.25 0.30 0.37  0.45 0.52  0.57 0.65  0.78 0.93  1.08  1.26  1.51  1.75  2.04

gas volume  

ft

3

/min  211  293  360 411  519  633  775  946  1098  1211 1368 1657  1967 2299 2671 3203  3717 4332

Flue Gas CO

at 

195ºC 

% 10.0 10.1 10.0 10.2  9.9  9.9  10.2  9.9  9.8  10.0 10.0 10.0  10.0  10.1  10.2  10.2  10.2  10.2

Table 3 Gas firing Data

Assembly and Installation Instructions for Ideal Vanguard L heating boilers should be read in conjunction 

with the general technical data tables enclosed and any other technical publication supplied with the burner.

Содержание Vanguard L 1100

Страница 1: ...you can be assured conform to the safety and performance specification that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy o...

Страница 2: ...60 90 60 90 60 90 Safety thermostat setting C 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 High low setting C 54 84 54 84 54 84 54 84 54 84 54 84 54 84 54 84 54 84 54 84 54...

Страница 3: ...ficiency operation ease of maintenance fuel flexibility and low emissions Suitable for oil or gas operation the Vanguard L range is supplied in a choice of 18 standard models rated in outputs from 130...

Страница 4: ...ACENT TO THE BOILER EN 304 Test code for heating boilers for atomizing oil burners 73 23 EEC Low voltage directive Relevant standard is EN60335 1 89336 EEC Electromagnetic Compatibility Directive Rele...

Страница 5: ...lime reduces the heat transfer from metal to water by 10 In practice the deposition of these salts is liable to cause noises from the boiler body or even premature boiler failure Corrosion and the fo...

Страница 6: ...170 630 T1 Flow connection T2 Return connection T3 Safety valve and expansion connection T4 Drain connection T5 Flue connection T6 Burner connection Boiler Size 170 240 290 340 420 510 630 Dimension A...

Страница 7: ...E T1 N O P T3 T2 I H T6 T4 T5 T1 T3 T2 1 2 3 4 41 11 16 17 30 24 12 13 21 14 15 22 23 40 van8099 Boiler Size 760 870 970 Dimension A mm 1122 1122 1122 Dimension B mm 1605 1800 1995 Dimension C mm 1432...

Страница 8: ...dimensions for boiler room access requirements Boiler Size 1100 1320 1570 1850 2200 2650 3000 3500 Dimension A mm 1352 1352 1462 1462 1622 1622 1720 1970 Dimension B mm 1952 2292 2282 2652 2692 3014 3...

Страница 9: ...oned so that there is enough space available to allow the following Access around the boiler for servicing Space to open the boiler front door Space to access the burner Recommended minimum clearances...

Страница 10: ...of the system 4 The boiler is at the highest point of the system Systems designed to rise above the flow connections will of course automatically require a minimum static head higher than shown 5 The...

Страница 11: ...g Other British Standards applicable to commercial sealed systems are BS6880 Part 2 BS 1212 BS 6281 Part 1 BS 6282 Part 1 BS 6283 Part 4 8 Ventilation Safe efficient and trouble free operation of conv...

Страница 12: ...shall be inclined upwards at 45 9 Fluing Flue Size Refer to applicable regulations while determining the size and height of the flue Please note that Vanguard L boilers have pressurised and sealed com...

Страница 13: ...ght Jacket 1 Upper Rear Central Left Jacket 1 Support for the Upper Jacket 1 Body Insulation 1 1 1 1 1 1 Front Insulation 1 1 1 1 1 1 Rear Insulation 1 1 1 1 1 1 Central Body Insulation 1 1 Rear Side...

Страница 14: ...M16 8 8 8 8 8 8 8 16 16 16 16 16 16 16 16 16 16 16 M12x60 M12x60 M16x70 M16x70 M16x70 M16x70 M16x70 M16x70 M16x70 M16x70 M20x80 M20x80 M20x80 M20x80 M20x80 M20x80 M120x80 M20x80 1 1 1 1 1 1 1 1 1 1 1...

Страница 15: ...nels 3 and 4 D Fit the rear insulation 6 fix the rear lower and upper retaining strips 7 and 8 with the self tapping screws Fit the plastic cable clamps 9 to the upper rear panel 8 E Fit the Ideal bad...

Страница 16: ...3 4 van8103 16 Position of thermometer thermostat sensor in the bulb holder Vanguard L 170 to 970 LEGEND 1 Thermometer bulb 2 Operation thermostat bulb 3 Safety thermostat bulb 4 Minimum temp thermost...

Страница 17: ...r insulation 7 fix the rear lower panels 9 with pins and springs and the upper panel 10 with the self tapping screws 8 Fit the plastic cable clamps 11 to the upper rear panel 10 E Fit the Ideal badge...

Страница 18: ...the plastic cable clamps 8 to it E Fit the Ideal badge to the front edge of the front top panel 9 and secure with the rubber fixings F Fit the control panel to front top panel 9 Remove the upper shell...

Страница 19: ...front edge of the front top panel 8 and secure with the rubber fixings F Fit the control panel to front top panel 8 Remove the upper shell of the control panel and insert the capillaries of thermomete...

Страница 20: ...ok them to the screws fitted to the upper square tube To determine which one of the front side panels is the left or the right ensure that the cable clamp plates 7 are positioned facing toward the fro...

Страница 21: ...ostat 3 Safety thermostat 4 Minimum thermostat Ensure that the sensors are inserted to the bottom of the bulb holder and then secure them with the retaining clip 5 In case some other thermostat is nec...

Страница 22: ...mber can be achieved through adjustment of the screws 23 Door Assembly Vanguard L 170 to 630 Models The combustion chamber door is fitted with four fixing points two on the left hand side which are no...

Страница 23: ...when reversing the door the bushing 9 nut 10 and washer 11 will have to be moved as shown below details 1 and 3 for hinge side details 2 and 4 for hinge side Door Adjustment 1 Vertical door adjustmen...

Страница 24: ...be and the hole in the door insulation Gas Supply The gas supply MUST be sized in accordance with British Gas recommendations and be prefabricated in compliance with CP 331 Pt 1 and any Local Gas Boar...

Страница 25: ...ur meter not supplied High low regulating thermostat Minimum thermostat Safety thermostat with manual reset N B With three phase the motor must be connected directly in this case the instrument panel...

Страница 26: ...tting Live on this lead hence on T2 allows burner to fire on low fire in a 2 stage burner No 10 S3 Burner lockout indicator Feeds signal from lockout terminal on burner control box to a remote lock ou...

Страница 27: ...FF Switch illuminated Position I ON Position OFF 12 Burner Switch Position I ON Position OFF 13 Pump Switch Position I I ON Position OFF 21 Boiler ON OFF High Low Thermostat High fire 54 C 84 C low fi...

Страница 28: ...tors will be placed inside the relevant smoke pipes at a distance from the front tube plate as shown in the picture on the right When using the boiler at minimum output the smoke temperature will not...

Страница 29: ...and drain down to complete the flushing process c Refill and vent the system clear all air locks and again check for water soundness d Balance the system 3 Finally set the controls to the User s requ...

Страница 30: ...freezing Otherwise drain the system completely 39 Safety For boilers with gas burners It is the law that any service work must be carried out by a Gas Safe Registered Engineer WARNING Always turn off...

Страница 31: ...es 4 Close off the fuel supply to the burner 5 Ensure that the boiler has been cooled to ambient temperature 6 Isolate the mains supply to the boiler and burner 7 Open the combustion chamber door afte...

Страница 32: ...Technical Helpline 01482 498 376 www idealheating com Ideal Boilers P O Box 103 National Ave Kingston upon Hull HU5 4JN Telephone 01482 492 251 Fax 01482 448 858 Registration No London 322 137 Ideal...