Operating instructions
AREA EXPERT:
LEVEL
DESCRIPTION
REGULATION
BUS-ID HS
Boiler Bus address only for cascade of E8 controllers
----
(01 - 08)
BUS ID 1
The heating circuits are sequentially numbered.....
01
(01 - 15)
BUS ID 2
The heating circuits are sequentially numbered.....
--
(01 - 15)
AF SUPPLY
Outdoor sensor power supply
01
(01 - 15)
BUS TERM
Bus terminating resistor
01
(00 - 01)
EBUS SUPPLY
Switching eBUS supply on/off in realtion to connected ....
01
(00 - 01)
TIME MASTER
00 no time master; 01 controller is time master
00
(01 - 01)
MAX T-COLL
Protects the HS from overheating
85°C
(30 - 110)
MIN T-COLL
Decreased condensation build-up in HS with low heat requirem.
10°C
(10 - 80)
MAX T-HS2
Protects the HS from overheating
85°C
(30 - 110)
MIN T-HS2
Decreased condensation build-up in HS with low heat requirem.
10°C
(10 - 80)
V-CURVE
Only for 0-10V input/output
11°C
(00 - 11)
CURVE 11 - U1
Low voltage set
1 V
(0 V-10 V)
CURVE 11 - U2
Higth voltage set
10 V
(0 V-10 V)
CURVE 11 - T1
Low temperature level
20°C
(0 - 120)
CURVE 11 - T2
Higth temperature level
85°C
(0 - 120)
CURVE 11 - UO
Starting with this voltage level
2 V
(0 V-10 V)
WARM-UP-T
Warm-up relief
35°C
(10 - 85)
MIN-DELIMI
Minimum delimiter HS
0
(01 - 03)
HYSTERESIS
Dyn. Switching hysteresys stage 1
5
(2K - 20K)
FOUND MODULS
Display of heat generators automatically reported via BUS
0
(0-30 min)
CAP/MODULE
After restarting the controller searches the bus systems
----
(0-1000)
NEW CONFIG
If the BUS configuration was modified, the automatic ..
(00 - 01)
MIN MOD CASC
When the casacade is started the number of stages.....
0
(00 - 100)
HW-BOILER
Number of stages for HW operation
0
(00 - 08)
CONTR DEVIAT
Header control variance
(00 - 08)
DES OUPUT
Required system output [in %]
(0 - 100)
SWITCH TIME
Internal control value: only for switching cascade
(-99 - 99)
BLOCK TIME
Currently remaining value
MAX T-MODUL
Maximum temperature of the heat generator
90°C
(50 - 110)
DYN UPWARD
Dynamic heat generator connection
300
(20 - 500)
DYN DOWNWARD
Dynamic heat generator deactivation
200
(20 - 500)
RESET TIME
Resetting time for I-Controller
50
(5 - 500)
IMODULAT MAX
If this modulation degree is exceeded, the next heat .....
30
(5 - 100)
MODULAT MIN
If values drop this modulation degree, the last heat
35
(10
- 60)
IND MOD MIN
Connection of the next heat generator
35
(0
- 60)
MOD LEVEL HW
Entry of the set modulation degree for the heat generators
80
(40
- 100)
SEQUENCE 1
Boiler sequence 1
12345678
SEQUENCE 2
Boiler sequence 2
87654321
MODIF SEQ
Sequence change mode
06
(01
- 06)
SEQ SW TIME
Time to sequence change
200
(10
- 800)
LOCK TIME
Min. delay time after switching on or with switching HS
00
(00
- 30)
HYST BURNER2
Solid fuel integration: hysteresiys for the charging pump
2
(2
- 20)
HS COOL-FCT
not used
0
(0
- 1)
T-HS COOL
not used
80
(50
- 95)
HEATSOURCE 1
Primary heat generator type
06/02 (00
- 06)
HS 1 BUS
connections for HS
02/03 (00
- 04)
INSTALLAZ
Range
Set