78
CHAPTER
1
3
CHAPTER 13 - EXTERNAL MODULATING CONTROL
HEATING SETTING
FACTORY
DEFAULT
MINIMUM
SETTING
MAXIMUM
SETTING
EZ SETUP RESET INSTALLER RESET
EXALT Solo
EXALT Combi
DHW Operation
Enabled
Enabled
✓
Demand Type
Thermostat
N/A
Thermostat
DHW Boiler Setpoint
168°F [75°C]
168°F [75°C]
96°F [35°C]
188°F [87°C]
✓
✓
DHW Setpoint
140°F [60°C]
140°F [60°C]
68°F [20°C]
168°F [75°C]
✓
✓
DHW Warmstart Setpoint
N/A
125°F [52°C]
86°F [30°C]
140°F [60°C]
✓
✓
DHW Warmstart Hysteresis
N/A
30°F [17K]
9K
36K
✓
✓
DHW On Differential
6°F [3K]
18°F [10K]
4°F [2°C]
18°F [10°C]
6°F [3K]
DHW Storage Adder
27°F [15°K]
N/A
10°F [5°C]
54°F [30°C]
27°F [15°K]
DHW Post Pump Time
2 Minutes
2 Minutes
Off
30 Minutes
✓
DHW Priority Timeout
Off
Off
Off
120 Minutes
✓
✓
DHW Priority
Enabled
Enabled
✓
DHW Call Blocking
1 Minute
1 Minute
0 Minute
30 Minutes
✓
DHW to CH Call Blocking
1 Minute
1 Minute
0 Minute
30 Minutes
✓
Antilegionella Function
Disabled
Enabled
Enabled
✓
BOILER SETTING
FACTORY
DEFAULT
MINIMUM
SETTING
MAXIMUM
SETTING
EZ SETUP RESET
INSTALLER RESET
EXALT Solo EX-
ALT Combi
Lockout Temp.
210°F [99°C]
✓
Modbus Address
0=BCST
0=BCST
247
✓
Flex. Relay 1(CH)
CH1
✓
Flex. Relay 2(DHW)
DHW
Flex. Relay 3(P3)
CH1/CH2/DHW
Flex. Relay 4(ERR)
ERROR
Flex. Relay 5(Flame)
FLAME
Flex. Relay 6(P4)
CH2
Error Relay
On Lockout, Blocking
and Warning
Pump PWM Minimum
30%
1%
100%
Ignition Level
Varies by model
Mix Zone High Limit
114°F [45°C]
68°F [20°C]
176°F [80°C]
Appliance Setting
Varies by model
Altitude Setting
0 ft
0 ft
20,000 ft
CTRLMax Factory Settings (cont’d)
Содержание EXALT Solo 110
Страница 2: ...INTENTIONALLY LEFT BLANK...
Страница 16: ...INTENTIONALLY LEFT BLANK...
Страница 24: ...INTENTIONALLY LEFT BLANK...
Страница 48: ...INTENTIONALLY LEFT BLANK...
Страница 56: ...INTENTIONALLY LEFT BLANK...
Страница 78: ...INTENTIONALLY LEFT BLANK...
Страница 88: ...INTENTIONALLY LEFT BLANK...
Страница 92: ...INTENTIONALLY LEFT BLANK...
Страница 94: ...INTENTIONALLY LEFT BLANK...
Страница 112: ...INTENTIONALLY LEFT BLANK...
Страница 125: ......
Страница 126: ......
Страница 127: ......
Страница 128: ...Ideal 1240 Forest Parkway Suite 100 West Deptford NJ 08066 Tel 800 411 9999 Fax 856 228 3584 E mail info idealusa com...