SYSTEM CONFIGURATIONS

The Multiline Flue Cascade is one of the latest additions to the flue accessory range from Ideal, designed 
specifically for the Evomax range. Available for installations up to 600kW as both a starter kit and extension pack 
the Multiline system enables Evomax boilers installed as open flue to be connected via a common flue header. This 
creates a single flue connection point for a flue specialist to design to knowing that the boiler installation is efficient 
and safe.

The Cascade flue system is supplied in two kits. A Starter Kit & an Extension Kit.
Wire retaining clips are also provided to prevent movement of the tube connections 
due to expansion and contraction. These must be fitted to the ductwork to ensure safe 
operation of the system.

•  Simple system ordering with a 

starter kit and extension kits

•  Starter kit includes, appliance 

connection, non-return flue damper, 
condensate tee and trap and all 
clips to secure the flue

•  Extension pack includes appliance 

connection, non-return flue damper, 
and all clips to secure the flue

•  Available for both 80/125 & 100/150 

flue adaptor applications

• For installations up to 600kW

• Type B23 flue

•  Designed specifically to work  

efficiently with Evomax appliances 
with commissioning simply 
completed by selecting Multiline  
flue from the installer set up menu

•  The perfect addition for Evomax 

installations using either the 
standard height or low frame and 
header kits

PRODUCTS

STARTER KIT

EXTENSION KIT

1

End Cap

R

2

Siphon / Condensate trap

R

3

Collector Pipe (200 dia)

R

R

4

Elbow (90 x 100)

R

R

5

Non-Return Valve Connector (100 x 150)

R

R

6

Non-Return Valve Body (150 x 100 or 80)

R

R

7

Flue Extension Tube (100 or 80)

R

R

8

Air Intake Grill

R

R

9

Flue Connector (100/150 or 80/125)

R

R

OPTION

GAS TYPE

EVOMAX MODELS

MAX NUMBER  

OF BOILERS

MAX SYSTEM

CAPACITY

1

Natural gas

Combinations of 100,

120, 150

6

600kW

2

Combinations

that include a

30, 40, 60 or 80

6

400kW

3

Propane

Combinations of

30P, 40P, 60P, 80P

6

400kW

MULTILINE CASCADE

The Multiline Flue Cascade is one of latest additions to the fl ue accessory range from 

Ideal, designed specifi cally for the Evomax range. Available for installations up to 

600kW as both a starter kit and extension pack the Multiline system enables Evomax 
boilers installed as open fl ue to be connected via a common fl ue header. This creates 
a single fl ue connection point for a fl ue specialist to design to knowing that the boiler 

installation is effi cient and safe.

MULTILINE FLUE CASCADE.

EVOMAX.

• 

Simple system ordering with a starter kit 
and extension kits

 

• 

Starter kit includes, appliance 
connection, non-return fl ue damper, 
condensate tee and trap and all clips to 
secure the fl ue

• 

Extension pack includes appliance 
connection, non-return fl ue damper, and 
all clips to secure the fl ue

• 

Available for both 80/125 & 100/150 fl ue 
adaptor applications 

  For installations up to 600kW

  Designed specifi cally to work 

effi ciently with Evomax appliances with 
commissioning simply completed by 
selecting Multiline fl ue from the installer 
set up menu

  The prefect addition for Evomax 

installations using either the standard 
height or low frame and header kits

Ideal Commercial Boilers
PO Box 103, National Avenue
Kingston upon Hull
East Yorkshire, HU5 4JN

T: 01482 440237
[email protected]

IDEALCOMMERCIALBOILERS.COM

The Cascade fl ue system is supplied in two kits. A Starter Kit & Extension Kit.

Wire retaining clips are also provided to prevent movement of the tube connections by the infl uence of

expansion and contraction. These must be fi tted to the ductwork to ensure safe operation of the system.  

PRODUCTS

STARTER KIT

EXTENSION KIT

1

End Cap

P

2

Siphon

P

3

Collector Pipe (200 dia)

P

P

4

Elbow (90

x 100)

P

P

5

Non-Return Valve Connector (100 x 150)

P

P

6

Non-Return Valve Body (150 x 100 or 80)

P

P

7

Flue Extension Tube (100 or 80)

P

P

8

Air Intake Grill

P

P

9

Flue Connector (100/150 or 80/125)

P

P

CASCADE FLUE KITS

OPERATION

*Control setting

Содержание Evomax 30

Страница 1: ...EVOMAX CONDENSING BOILER PRODUCT FLUE GUIDE WE HAVE IT COVERED...

Страница 2: ...g industry Your phone or tablet can let you appreciate our Evomax range in a new dimension The Ideal Commercial Eye app uses the latest technology to project 3D renders from the page of this brochure...

Страница 3: ...2 Introduction 4 13 Evomax 30 150kW 14 25 Evomax Cascade 30 600kW 26 37 Evomax Flue Options 38 39 Flue Types 40 46 Guide to Flue Installation Regulation 47 Condensate Pumps 48 49 Ideal Training Suppo...

Страница 4: ...04 EVOMAX 30 150kW 5 year warranty subject to Terms and Conditions 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers...

Страница 5: ...05...

Страница 6: ...1 turndown Compact one width height for easy siting Simple controls interface with large backlit display Comprehensive range of flue fixing and control options Designed for easy installation commissi...

Страница 7: ...150 610 233 120 The following minimum clearances must be maintained for operation and servicing TOP DEPENDENT ON FLUE SIZE SIDES 25mm FRONT 450mm BOTTOM 300mm CLEARANCE BETWEEN MULTIPLE BOILER INSTAL...

Страница 8: ...12 2 15 2 16 4 20 5 20 5 24 6 30 7 Gross kW 6 7 6 6 9 0 8 8 13 5 16 5 18 2 22 2 22 7 27 3 34 1 Gas Rate Max rate m hr 3 2 1 26 4 3 1 69 6 4 2 53 8 7 3 41 10 8 13 0 16 2 Flue Gas Flow Rate Max Rate m...

Страница 9: ...ontent l 3 0 5 0 7 0 9 2 Dry Weight Kg 49 60 30 75 70 89 75 Optional kit available on 60 80 models for 100 150mm flue For use with vertical flues only BOILER EVOMAX Remote indication run alarm Hours r...

Страница 10: ...mixed output cascades The boiler must have a maximum operating pressure of 6 bar and be suitable for heating and indirect hot water systems DIMENSIONS The condensing boiler range must have a universal...

Страница 11: ...that fitting must be subtracted from the maximum flue extensions allowed for that flue option Note Horizontal terminal resistance includes 1 x 90 elbow When installing Evomax boilers with concentric...

Страница 12: ...EATING CIRCUITS PRIMARY HWS 1 HWS SENSOR FROM HEATING CIRCUITS P1 P2 P3 S2 TO DRAIN S3 TANK SECONDARY HWS 1 P5 LOW LOSS MIXING HEADER SYSTEM LAYOUT TYPICAL SYSTEM BOILER LAYOUT Low loss header may not...

Страница 13: ...13...

Страница 14: ...14...

Страница 15: ...15 EVOMAX CASCADE 30 600kW...

Страница 16: ...are available for use with in line kits if required BACK TO BACK KITS Kits include all the in line contents plus the required special frame kits for such compact installations Both types of kit are a...

Страница 17: ...0 552 DN80 80 125 100kW 1945 1650 552 DN80 100 150 UIN209800 120 150kW 1945 1650 552 DN100 100 150 HEADER KITS RATING HEIGHT mm LENGTH mm DEPTH mm DN FLANGE SIZE CONCENTRIC FLUE UIN209803 30 80kW 1945...

Страница 18: ...5 2750 552 DN100 100 150 UIN209804 120kW 1945 2750 552 DN100 100 150 HEADER KITS RATING HEIGHT mm LENGTH mm DEPTH mm DN FLANGE SIZE CONCENTRIC FLUE UIN209806 30 80kW 1945 3300 552 DN100 80 125 100kW 1...

Страница 19: ...00 930x1096 209901 190 3 30 60 100 2030 x 573 209801 30 60 100 480x1096 209903 200 2 100 1480 x 573 209799 100 930x1096 209901 210 4 30 40 60 80 2580 x 552 209803 30 40 60 80 1480x950 209905 220 3 2 x...

Страница 20: ...209806 40 80 4 x 100 2030x1096 209908 530 6 30 5 x 100 3680x573 209806 30 5 x 100 2030x1096 209908 540 4 2 x 120 2 x 150 2580x663 209802 2 x 120 2 x 150 1480x1276 209904 550 N A N A N A N A N A N A 5...

Страница 21: ...e boiler the flow and return flexible connections which reduce installation time Delivered with header kit connection pipe assembly non return valves pipe work connector all isolation valves pressure...

Страница 22: ...2 100 150 150kW 1550 1650 642 100 150 3 X EVOMAX 30 150 KW 1550 HEADER KITS HEIGHT mm LENGTH mm DEPTH mm DN FLANGE SIZE CONCENTRIC FLUE 30 80kW 1550 1100 642 DN65 80 125 100 120kW 1550 1100 642 100 15...

Страница 23: ...2 DN65 1100 x 642 209395 1 x 120 1 x 60 210029 180 2 DN65 1100 x 666 209395 1 x 150 1 x 30 210029 190 2 DN65 1100 x 666 209395 1 x 150 1 x 40 210029 200 2 DN65 1100 x 642 209395 2 x 100 210029 200 2 D...

Страница 24: ...x 30 210020 290 3 DN80 1650 x 666 252437 1 x 150 1 x 100 1 x 40 210020 300 3 DN80 1650 x 642 252437 3 x 100 210020 320 3 DN80 1650 x 642 252437 2 x 100 1 x 120 210020 320 3 DN80 1650 x 642 252437 2 x...

Страница 25: ...OILER PUMP HEATING PUMP TO HEATING CIRCUITS PRIMARY HWS 1 SECONDARY HWS 1 HWS SENSOR FROM HEATING CIRCUITS P2 P3 P4 P5 S2 S1 TO DRAIN TANK BOILER PUMP P1 TO DRAIN S3 LOW LOSS MIXING HEADER Low loss he...

Страница 26: ...26 EVOMAX FLUE OPTIONS...

Страница 27: ...27...

Страница 28: ...80 125 100 150 Wall flue kit No 213264 213266 EVOMAX 60 80 HORIZONTAL CONCENTRIC FLUES OF LONGER LENGTHS LARGER FLUE DIAMETER Model 60 60P 80 80P Max flue length m 30 35 Flue Size 100 150 Wall flue ki...

Страница 29: ...ust be fitted to all installations At least 1 off extension tube MUST be used in the installation This may be suitably cut to length if required To comply with CE certification Evomax boilers must be...

Страница 30: ...elbow B N A N A 158773 158774 4 45 elbow pair B N A N A 158775 158776 5 Flat Weather Collar B C 152611 152612 158780 158780 6 Pitched Weather Collar B C 152609 152610 158779 158779 7 1m Extension conc...

Страница 31: ...elbows is shown in Table 2 FLUE RESISTANCES FLUE SYSTEMS TABLE 1 TABLE 2 MAX PERMISSIBLE EQUIVALENT FLUE LENGTH INC TERMINAL RESISTANCE METRES CONCENTRIC OPEN FLUE Flue Size 80 125 100 150 80 100 Mod...

Страница 32: ...2 100 100 150 220 120 100 150 365 150 100 150 430 Therefore this installation is acceptable as only a 2m run FOR OWN BUILT OPEN FLUE USE THIS EXAMPLE 1 CONCENTRIC HORIZONTAL FLUE FOR EVOMAX 40 Resista...

Страница 33: ...17 6 2 x 90 elbow 2 x 1 9 3 8 Total Flue Resistance 17 6 3 8 13 8 b 9 5 3 5 0 1 2 6 0 2 b 7 5 3 5 0 1 2 6 0 2 EXAMPLE 2 CONCENTRIC VERTICAL FLUE FOR EVOMAX 80 Resistance m Flue Size 80 125 Max permiss...

Страница 34: ...100 120 150 6 600kW 2 Combinations that include a 30 40 60 or 80 6 400kW 3 Propane Combinations of 30P 40P 60P 80P 6 400kW MULTILINE CASCADE The Multiline Flue Cascade is one of latest additions to t...

Страница 35: ...erature Max Max Min Hmax Pmax 0 5 0 5 kW kW kW Pa C 30 7 5 400 40 9 7 9 0 72 40 10 60 15 80 20 100 25 600 80 120 30 150 37 5 30P 7 5 400 40 11 4 10 6 40P 10 60P 15 80P 20 At the maximum system capacit...

Страница 36: ...an be used to relocate the flue terminal up to 10m Suitable for all Evomax up to 120kW Available for both 80 125 100 150 flue applications Plume kit offers terminal relocation up to 10m Includes stand...

Страница 37: ...ME KIT 80 125 EVOMAX PLUME KIT 100 150 80 125 DIA FLUE MAXIMUM PERMISSIBLE FLUE LENGTHS M Evomax Model 30 30P 40 40P 60 60P 80 80P Y X 0 5 39 2 39 2 4 7 9 2 2 0 38 5 38 5 4 0 8 5 4 0 37 6 37 6 3 1 7 6...

Страница 38: ...n which a boiler s is installed which is not large enough to permit access for work other than maintenance via external access Plant room a room in a building that houses plant and machinery Open spac...

Страница 39: ...ducts to outside atmosphere C11 C12 C13 C2 appliance flue connects to a common duct system for multi appliance installations the common duct system is part of the building C21 C22 C23 C 3 appliance w...

Страница 40: ...industrial and commercial premises Building Regs Part J Combustion appliances and heat storage gives advice on how to comply with Building Regulations Clean Air Act A UK Parliament Act passed in resp...

Страница 41: ...s CLEAN AIR ACT THE FACTS The Act applies to gas and other fuels fired appliance installations generally but with specific requirements for installations exceeding 333 kW net heat input including appr...

Страница 42: ...above 70kW 80kW 100kW 120kW 150kW 200kW 240kW 300kW Open Flue and Fanned Draught 1500mm 1600mm 1790mm 1975mm 2265mm 2740mm 3120mm 3690mm For other open flue fan draught inputs use Distance 9 5156 x ne...

Страница 43: ...B Enclosure Summer usage greater than 50 up to 75 Summer usage greater than 75 up to 100 High 2 5 1 2 Low 4 10 1 2 for boilers in use for more than 50 of the time during the summer months additonal v...

Страница 44: ...ve to the outside atmosphere developing in the boiler room Interlocked to the gas appliance IMPORTANT The application of any other treatment to this product may render the guarantee of Ideal Boilers I...

Страница 45: ...as an air vent However in addition the outlet should not be nearer than 150mm fanned draught to an opening into the building fabric formed for the purpose of accommodating a built in element such as a...

Страница 46: ...al space it must itself be adequately ventilated as above The temperature within the boiler room shall not exceed 25 C within 100mm of the floor 32 C at mid height and 40 C within 100mm of the ceiling...

Страница 47: ...8amps Alarm contact NC 4 Amps resistive Overheat protection 130 C Tank Capacity 2 0 Litres Maximum vertical head 4 5m Maximum horizontal length 30m IDEAL COMMERCIAL BOILERS CONDENSATE PUMP COMPATABILI...

Страница 48: ......

Страница 49: ...d by a dedicated national service team delivering help and advice to you and your customers throughout the year SALES Tel 0844 5436060 Fax 0844 5436181 TECHNICAL Tel 01482 498376 Fax 01482 498621 comm...

Страница 50: ...50 NOTES...

Страница 51: ...51 NOTES...

Страница 52: ...vement in design and performance of its products and reserves the right to vary specification without notice Statutory rights of the consumer are not affected PLEASE NOTE The information in this broch...

Отзывы: