SYSTEM CONFIGURATIONS

The Multiline Flue Cascade is one of the latest additions to the flue accessory range from Ideal, designed 

specifically for the Evomax range. Available for installations up to 600kW as both a starter kit and extension pack 

the Multiline system enables Evomax boilers installed as open flue to be connected via a common flue header. This 

creates a single flue connection point for a flue specialist to design to knowing that the boiler installation is efficient 

and safe.

The Cascade flue system is supplied in two kits. A Starter Kit & an Extension Kit.
Wire retaining clips are also provided to prevent movement of the tube connections 

due to expansion and contraction. These must be fitted to the ductwork to ensure safe 

operation of the system.

•  Simple system ordering with a 

starter kit and extension kits

    Starter kit includes, appliance 

connection, non-return flue 

damper, 

condensate tee and trap and all 

clips to secure the flue

•  Extension pack includes appliance 

connection, non-return flue damper, 

and all clips to secure the flue

•  Available for both 80/125 & 100/150 

flue adaptor applications

• For installations up to 600kW
• Type B23 flue
•  Designed specifically to work  

efficiently with Evomax appliances 

with commissioning simply 

completed by selecting Multiline  

flue from the installer set up menu

•  The perfect addition for Evomax 

installations using either the 

PRODUCTS

STARTER KIT

EXTENSION KIT

1

End Cap

R

2

Siphon / Condensate trap

R

3

Collector Pipe (200 dia)

R

R

4

Elbow (90 x 100)

R

R

5

Non-Return Valve Connector (100 x 150)

R

R

6

Non-Return Valve Body (150 x 100 or 80)

R

R

7

Flue Extension Tube (100 or 80)

R

R

8

Air Intake Grill

R

R

OPTION

GAS TYPE

EVOMAX MODELS

MAX NUMBER  

OF BOILERS

MAX SYSTEM

CAPACITY

1

Natural gas

Combinations of 100,

120, 150

6

600kW

2

Combinations

that include a

30, 40, 60 or 80

6

400kW

3

Propane

Combinations of

30P, 40P, 60P, 80P

6

400kW

MULTILINE CASCADE

The Multiline Flue Cascade is one of latest additions to the fl ue accessory range from 

Ideal, designed specifi cally for the Evomax range. Available for installations up to 

600kW as both a starter kit and extension pack the Multiline system enables Evomax 

boilers installed as open fl ue to be connected via a common fl ue header. This creates 

a single fl ue connection point for a fl ue specialist to design to knowing that the boiler 

installation is effi cient and safe.

MULTILINE FLUE CASCADE.

EVOMAX.

• 

Simple system ordering with a starter kit 
and extension kits

 

• 

Starter kit includes, appliance 
connection, non-return fl ue damper, 
condensate tee and trap and all clips to 
secure the fl ue

• 

Extension pack includes appliance 
connection, non-return fl ue damper, and 
all clips to secure the fl ue

• 

Available for both 80/125 & 100/150 fl ue 
adaptor applications 

  For installations up to 600kW

  Designed specifi cally to work 

effi ciently with Evomax appliances with 
commissioning simply completed by 
selecting Multiline fl ue from the installer 
set up menu

  The prefect addition for Evomax 

installations using either the standard 
height or low frame and header kits

Ideal Commercial Boilers
PO Box 103, National Avenue
Kingston upon Hull
East Yorkshire, HU5 4JN

T: 01482 440237
[email protected]

IDEALCOMMERCIALBOILERS.COM

The Cascade fl ue system is supplied in two kits. A Starter Kit & Extension Kit.

Wire retaining clips are also provided to prevent movement of the tube connections by the infl uence of

expansion and contraction. These must be fi tted to the ductwork to ensure safe operation of the system.  

PRODUCTS

STARTER KIT

EXTENSION KIT

1

End Cap

P

2

Siphon

P

3

Collector Pipe (200 dia)

P

P

4

Elbow (90

x 100)

P

P

5

Non-Return Valve Connector (100 x 150)

P

P

6

Non-Return Valve Body (150 x 100 or 80)

P

P

7

Flue Extension Tube (100 or 80)

P

P

8

Air Intake Grill

P

P

9

Flue Connector (100/150 or 80/125)

P

P

CASCADE FLUE KITS

OPERATION

Содержание EVOMAX 2 30

Страница 1: ...EVOMAX 2 CONDENSING BOILER PRODUCT FLUE GUIDE...

Страница 2: ...g industry Your phone or tablet can let you appreciate our Evomax range in a new dimension The Ideal Commercial Eye app uses the latest technology to project 3D renders from the page of this brochure...

Страница 3: ...Introduction 4 11 Evomax 2 30 150kW 12 17 Evomax 2 Cascade 30 900kW 18 30 Evomax 2 Flue Options 31 32 Flue Types 33 39 Guide to Flue Installation Regulation 40 Condensate Pumps 42 Ideal Training Supp...

Страница 4: ...kW 5 year warranty subject to Terms and Conditions 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers Terms and conditions available at www idealcommercialboile...

Страница 5: ...5...

Страница 6: ...Up to 99 6 full load efficiency Up to 110 part load efficiency Exactly the same compact footprint as Evomax allowing for easy like for like replacement Dynamic control menu set up Cascade controls opt...

Страница 7: ...FRONT 450mm BOTTOM 300mm CLEARANCE BETWEEN MULTIPLE BOILER INSTALLATIONS 25mm KEY 1 Auto Air Vent 2 Burner Fixings 3 Fan 4 Gas Valve 5 Venturi 6 Flow Thermistor 7 Ignitor Unit 8 Electrode Detection 9...

Страница 8: ...7 96 2 96 4 97 2 96 7 96 6 96 7 SEDBUK 2009 89 6 89 3 89 4 n a n a n a n a Operating Temperature Max C 85 EVOMAX 2 30 150kW Natural Gas PERFORMANCE DATA MODEL 30P 40P 60P 80P 100P 120P Boiler Output n...

Страница 9: ...0 7 0 9 2 Dry Weight Kg 47 5 57 5 73 0 81 0 Optional kit available on 60kW and 80kW models for 100 150mm flue BOILER EVOMAX 2 Remote indication run alarm Hours run BMS 0 10v operation Pump overrun La...

Страница 10: ...g boiler range must have a universal compact width and height across the range to ensure mixed output cascades maintain the same universal configuration Maximum permitted wall area of 0 43m MOUNTING T...

Страница 11: ...om the maximum flue extensions allowed for that flue option Note Horizontal terminal resistance includes 1 x 90 elbow When installing Evomax boilers with concentric flue horizontally or vertically the...

Страница 12: ...12 EVOMAX 2 CASCADE 30 900kW...

Страница 13: ...e total number of boilers in the cascade Choose Hydraulic Separation select Plate Heat Exchanger or Low Loss Header Choose Pumps select the relevant pump for your cascade A few things to bear in mind...

Страница 14: ...Y 219550 6 boilers 30 150kW DN100 for PHEX 6 boilers 30 100kW DN100 for LLH 219546 6 boilers 120 150kW DN150 for LLH ONLY 219551 Standard Height Frame Back to Back boilers 2 boilers 30 150kW DN80 for...

Страница 15: ...N100 222995 Up to 300kW total output DN80 222225 Up to 450kW total output DN80 222226 Up to 450kW total output DN100 222996 Up to 600kW total output DN100 222227 Up to 750kW total output DN100 222228...

Страница 16: ...16 SYSTEM LAYOUT TYPICAL SYSTEM BOILER LAYOUT EVOMAX 2 FRAME HEADER KIT C W PLATE HEAT EXCHANGER LEGEND...

Страница 17: ...ION AND REFERENCE USE ONLY THE SCHEMATIC MAY NOT ACCURATELY DESCRIBE THE ACTUAL ARRANGEMENT REQUIRED IN ORDER FOR THE SYSTEM TO OPERATE CORRECTLY AND ADDITIONAL COMPONENTS MAY BE REQUIRED UNDER NO CIR...

Страница 18: ...18 EVOMAX 2 FLUE OPTIONS...

Страница 19: ...19...

Страница 20: ...x flue length m 33 30 17 5 10 10 9 6 Flue Size 80 125 100 150 Wall flue kit No 220915 220918 EVOMAX 2 60 80 HORIZONTAL CONCENTRIC FLUES OF LONGER LENGTHS LARGER FLUE DIAMETER Model 60 60P 80 80P Max f...

Страница 21: ...1 158772 Extension tube x2 The air inlet grille must be fitted to all installations At least 1 off extension tube MUST be used in the installation This may be suitably cut to length if required EVOMAX...

Страница 22: ...Weather Collar 100 150 152612 90 Elbow 80 125 single 213259 90 Elbow 100 150 single 213263 90 Elbow 80 125 Extended 222004 90 Elbow 100 150 Extended 222005 45 Elbow 80 125 single 213260 45 Elbow 100...

Страница 23: ...612 213259 213263 213260 213258 202242 202243 220916 220918 220919 220920 220921 213261 213262 152609 152610 152611 221216 158769 158770 158771 158772 158773 158776 152404 158774 158777 158775 152259...

Страница 24: ...of elbows is shown in Table 2 FLUE RESISTANCES FLUE SYSTEMS TABLE 1 TABLE 2 MAX PERMISSIBLE EQUIVALENT FLUE LENGTH INC TERMINAL RESISTANCE METRES CONCENTRIC OPEN FLUE Flue Size 80 125 100 150 80 100...

Страница 25: ...00 150 220 120 100 150 473 150 100 150 332 Therefore this installation is acceptable as only a 2m run FOR OWN BUILT OPEN FLUE USE THIS EXAMPLE 1 CONCENTRIC HORIZONTAL FLUE FOR EVOMAX 2 40 Resistance m...

Страница 26: ...ue Resistance 65 0 9 64 1 HORIZONTAL FLUE FOR EVOMAX 2 120 Resistance m Flue Size 100 150 Max permissible flue run 9 2 x 90 elbow 2 x 1 9 3 8 Total Flue Resistance 9 3 8 5 2 b 9 5 3 5 0 1 2 6 0 2 EXAM...

Страница 27: ...s that include a 30 40 60 or 80 6 400kW 3 Propane Combinations of 30P 40P 60P 80P 6 400kW MULTILINE CASCADE The Multiline Flue Cascade is one of latest additions to the ue accessory range from Ideal d...

Страница 28: ...0 72 40 10 60 15 80 20 100 25 600 80 120 30 150 37 5 30P 7 5 400 40 11 4 10 6 40P 10 60P 15 80P 20 At the maximum system capacity the static pressure generated against the flue resistance at position...

Страница 29: ...150kW the Plume Kit can be used to relocate the flue terminal up to 10m Suitable for all Evomax 2 up to 150kW Available for both 80 125 100 150 flue applications Plume kit offers terminal relocation u...

Страница 30: ...KIT 80 125 EVOMAX PLUME KIT 100 150 80 125 DIA FLUE MAXIMUM PERMISSIBLE FLUE LENGTHS M Evomax Model 30 30P 40 40P 60 60P 80 80P Y X 0 5 39 2 39 2 4 7 9 2 2 0 38 5 38 5 4 0 8 5 4 0 37 6 37 6 3 1 7 6 6...

Страница 31: ...boilers and ancillary plant Enclosure space in which a boiler s is installed which is not large enough to permit access for work other than maintenance via external access Plant room a room in a buil...

Страница 32: ...ducts to outside atmosphere C11 C12 C13 C2 appliance flue connects to a common duct system for multi appliance installations the common duct system is part of the building C21 C22 C23 C 3 appliance w...

Страница 33: ...industrial and commercial premises Building Regs Part J Combustion appliances and heat storage gives advice on how to comply with Building Regulations Clean Air Act A UK Parliament Act passed in resp...

Страница 34: ...llations CLEAN AIR ACT THE FACTS The Act applies to gas and other fuels fired appliance installations generally but with specific requirements for installations exceeding 333 kW net heat input includi...

Страница 35: ...above 70kW 80kW 100kW 120kW 150kW 200kW 240kW 300kW Open Flue and Fanned Draught 1500mm 1600mm 1790mm 1975mm 2265mm 2740mm 3120mm 3690mm For other open flue fan draught inputs use Distance 9 5156 x ne...

Страница 36: ...er usage greater than 75 up to 100 High 2 5 1 2 Low 4 10 1 2 for boilers in use for more than 50 of the time during the summer months additional ventilation needs to be added to those in columns A and...

Страница 37: ...ve to the outside atmosphere developing in the boiler room Interlocked to the gas appliance IMPORTANT The application of any other treatment to this product may render the guarantee of Ideal Boilers I...

Страница 38: ...as an air vent However in addition the outlet should not be nearer than 150mm fanned draught to an opening into the building fabric formed for the purpose of accommodating a built in element such as a...

Страница 39: ...al space it must itself be adequately ventilated as above The temperature within the boiler room shall not exceed 25 C within 100mm of the floor 32 C at mid height and 40 C within 100mm of the ceiling...

Страница 40: ...50 60 Hz 0 8amps Alarm contact NC 4 Amps resistive Overheat protection 130 C Tank Capacity 2 0 Litres Maximum vertical head 4 5m Maximum horizontal length 30m IDEAL COMMERCIAL BOILERS CONDENSATE PUMP...

Страница 41: ...41...

Страница 42: ...by a dedicated national service team delivering help and advice to you and your customers throughout the year SALES Tel 0844 543 6060 Fax 0844 543 6181 TECHNICAL Tel 01482 498376 Fax 01482 498621 com...

Страница 43: ...43 NOTES...

Страница 44: ...eal Commercial Boilers has a policy of continuous development and therefore reserves the right to alter product specifications or any other details without prior notification PLEASE NOTE The informati...

Отзывы: