4
Concord CX
- Installation
Boiler
CX 40
CX 50
CX 60
CX 70
CX 80
CX 90
CX 100
Number of sections
3
4
4
5
5
6
6
Boiler Input
Nett
kW
47.3
56.3
67.7
79.2
90.7
102.3
112.6
Btu/h (x 1000)
161.4
192.1
230.9
270.3
309.6
349.0
384.2
Gross
kW
52.5
62.5
75.1
87.93
100.7
113.5
125.0
Btu/h (x 1000)
179.1
213.3
256.2
300
343.6
387.3
426.5
Boiler output to water
kW
42.0
50.0
60.08
70.34
80.56
90.8
100.0
Btu/h (x 1000)
143.3
170.6
205.0
240.0
274.9
309.8
341.2
Gas rate
m
3
/h
5.0
5.96
7.16
8.38
9.6
10.82
11.91
(ft
3
/h)
(176.6)
(210.5)
(252.9)
(295.9)
(339.0)
(382.1)
(420.6)
Approximate
4.5% CO
2
&100°C.
44
52
63
73
84
94
104
flue gas volume
dm
3
/s
in the secondary
flue of the chim-
4.5% CO
2
& 212°F.
93
110
133
155
178
199
220
ney system
ft.
3
m
Manifold setting pressure
mbar
11.7
10.5
12.2
10.4
10.3
11.2
11.5
(in.w.g.)
(4.7)
(4.2)
(4.9)
(4.2)
(4.1)
(4.5)
(4.6)
Seasonal efficiency (SEDBUK)*
[72.0]%
[72.4]%
[73.5]%
[72.6]%
[73.2]%
[73.4]%
[73.8]%
Table 1- Performance Data
Boiler
CX 40
CX 50
CX 60
CX 70
CX 80
CX 90
CX 100
Number of sections
3
4
4
5
5
6
6
Flow tappings
Rc (in. BSP)
2 x 2 at rear
Return tappings
Rc (in. BSP)
2 x 2 at rear
Maximum static head
metres (feet)
45.7 (150)
Maximum pressure
bar (p.s.i.)
4.5 (65)
Gas inlet connection
Rc (in. BSP)
3/4 (3/4)
1 (1 )
Minimum dynamic
mbar
gauge
15.0
15.0
16.2
15.0
15.0
15.0
15.4
gas pressure required
at the boiler inlet
(in.w.g.)
(6.0)
(6.0)
(6.5)
(6.0)
(6.0)
(6.0)
(6.2)
Electricity supply
230 Volts- single phase, 50 Hz, fuse 5 A
Nominal flue size (to BS. 835)
mm
150
150
175
175
200
200
200
(in.)
(6)
(6)
(7)
(7)
(8)
(8)
(8)
Diverter outlet socket
mm
184
184
213
213
238
238
238
internal diameter
(in.)
(7.3)
(7.3)
(8.4)
(8.4)
(9.4)
(9.4)
(9.4)
Length of burner bars (overall)
mm
377
497
497
617
617
737
737
(in)
(14.8)
(19.5)
(19.5)
(24.3)
(24.3)
(29.0)
(29.0)
Main burner injectors (3 off)
size, mm
3.4
3.82
4.12
4.57
4.86
5.2
5.3
Approximate dry weight
kg
210
265
265
330
330
395
395
(lb.)
(463)
(584)
(584)
(727)
(727)
(871)
(871)
Water content
litre
22
30
30
37
37
45
45
(gal.)
(4.8)
(6.6)
(6.6)
(8.2)
(8.2)
(9.9)
(9.9)
Table 2 - General Data
Note.
To obtain gas consumption, divide gross heat input (kW) by a calorific value of 37.8 (MJ/m
3
)
GENERAL
*
The value is used in the UK government's Standard Assessment Procedure (SAP) for energy rating of dwellings.
The test data from which it has been calculated have been certified by BGplc 0087.