Ideal Heating IMAX XTRA 2 Скачать руководство пользователя страница 3

3

Conversion Kit

KIT CONTENTS

LEGEND

A. 

4 off -  M5 x

12 mm bolts

B. Self adhesive Natural Gas data plate
C. 

O-ring

A

C

B

SAFETY

EXAMPLE:                VR                           22546400000001

FOR NATURAL GAS ONLY

PO BOX 103, NATIONAL AVENUE, HULL,

EAST YORKSHIRE, HU5 4JN

MAX. FLOW TEMPERATURE 90`C

kW (Btu/h)

 I.P.20

NOX CLASS 6

24.0(81,900)

23.3(79,500)

kW (Btu/h)

BOILER TYPE:C

53

 C

63

 B

23

 

78.6(268,200)

M A X .

25.8(88,000)

N O N - C O N D ' G

WITH A GOVERNED METER

MADE IN THE UK BY IDEAL BOILERS LTD.

kW (Btu/h)

26.6(90,750)

HEAT OUTPUT "P" = 

M I N .

HEAT INPUT "Q" =

COUNTRIES OF DESTINATION: GB, IE

NET

OPERATING WATER PRESSURE

PMS = 6.0 bar MAX, 0.3 bar MIN

2797

CAT.I

2H

 NATURAL GAS

230V  50HZ FUSED AT 13A

2H-G20-20mbar

M I N .

82.2(280,450)

POWER CONSUMPTION 110W

88.8(303,000)

M A X .

kW (Btu/h)

GROSS

80.0(272,950)

CONDENSING

80kW IM

AX X

TR

A 2

80kW IM

AX X

TR

A 2

CE 682118

80kW IMAX XTRA 2

RECORD THE ORIGINAL BOILER DETAILS

 BOILER TO BE INSTALLED 

GAS SUPPLY PRESSURE 20mbar

IMPORTANT

After completing the servicing or replacement of components always:

•  Test for gas soundness.

•  Check the water system is correctly filled and free of air.  Air in the boiler 

could cause damage to the heat exchanger.

 

With the system hot examine all water connections for soundness.

•  Check the gas rate and measure the combustion CO/CO

2

 content.  The 

CO/CO

2

 ratio of the flue gas should not be greater than 0.004 ratio & the 

CO should not exceed 350ppm. 

•  Carry out functional checks as appropriate.

It is the law that any service work must be 

carried out by a Suitably qualified Gas Safe 

Registered Engineer.  In IE service work 

must be carried out by a competent person.

WARNING

ALWAYS TURN OFF THE GAS SUPPLY 

AT THE GAS SERVICE COCK, AND 

SWITCH OFF AND DISCONNECT 

THE ELECTRICITY SUPPLY TO THE 

APPLIANCE AND ANY EXTERNAL 

CONTROLS BEFORE SERVICING OR 

REPLACING COMPONENTS.

Содержание IMAX XTRA 2

Страница 1: ...nditioned or copy parts that have not been clearly authorised by Ideal Heating For the very latest copy of literature for specification and maintenance practices visit our website idealheating com whe...

Страница 2: ...ailure to install appliances correctly could lead to prosecution It is in your own interest and that of safety to ensure the law is complied with kW NG Product No Imax Xtra 2 80 225464 Imax Xtra 2 120...

Страница 3: ...682118 80kWIMAXXTRA2 RECORDTHE ORIGINALBOILER DETAILS BOILERTO BE INSTALLED GAS SUPPLY PRESSURE 20mbar IMPORTANT After completing the servicing or replacement of components always Test for gas soundne...

Страница 4: ...s and remove Front Panel 3 Remove the 3 bolts along the top of the front panel The bolts are visible when the control pod is removed Pull the panel forwards at the top lift out of bottom slot and remo...

Страница 5: ...re it is secure 3 Replace the four bolts that have been removed with the four new M5 x 12mm bolts supplied in the conversion kit Ensure an even tightening sequence of the bolts REMOVING THE ORIFICE PL...

Страница 6: ...L Performing this action will reconfigure using current configuration settings Are you sure NEXT Boiler Power 80kW Gas Type Boiler Power Set NG 80kW 11 Gas Type NEXT NEXT CONFIRM Yes Yes Config User M...

Страница 7: ...rate without modulating set the fan speed to minimum following the steps in the gas valve adjustment diagram on the next page 5 Using the minimum rate adjustment screw adjust the valve until the CO2...

Страница 8: ...ure Return Temperature Flame Current 6800 rpm 6800 rpm 10 Minutes 75 c 60 c 5 7 A MAX RATE To set the boiler to run at Maximum Rate for 10 Minutes press Maximum Rate The boiler will run at Maximum Rat...

Страница 9: ...the two tear off strips 4 Once all details have been recorded adhere one of the two tear off strips over the existing label at the rear of the boiler and the other one over the existing label on the...

Страница 10: ...Conversion Kit 10 NOTES...

Страница 11: ...Conversion Kit 11 NOTES...

Страница 12: ...Heating we take our environmental impact seriously therefore when installing any Ideal Heating product please make sure to dispose of any previous appliance in an environmentally conscious manner Hous...