9
idealheating.com
8
welcome to our ideology
INCLUDED AS STANDARD
OPTIONAL KITS
GENERAL DATA
EVOMAX 2 30 - 150kW (Natural Gas & LPG)
*Optional kit available on 60kW and 80kW models for 100/150mm flue
PERFORMANCE DATA
EVOMAX 2 30 - 150kW (Natural Gas)
EVOMAX 2 30 - 120kW (LPG)
MODEL
30
40
60
80
100
120
150
Boiler Output (non-condensing)
Mean 70°C
Max
kW
30
40
60
80
100
120
150
Min
kW
6
8
12
16
20
24
30
Boiler Output (condensing) Mean
40°C
Max
kW
31.5
42.0
63.5
84.4
103.9
124.7
158
Min
kW
6.5
8.5
12.7
17.2
21.6
26.0
32.5
Boiler Input Max Rate
Net
kW
30.4
40.5
60.8
82.0
102.4
122.9
153.7
Gross
kW
33.7
44.9
67.4
90.9
113.6
136.4
170.5
Boiler Input Min Rate
Net
kW
6.1
8.1
12.2
16.4
20.5
24.6
30.7
Gross
kW
6.7
9.0
13.5
18.2
22.7
27.3
34.1
Gas Rate
Max rate
m
³
/hr
3.2
4.3
6.4
8.7
10.8
13.0
16.2
Flue Gas Flow Rate
Max Rate
m
³
/hr
41.30
54.05
80.65
110.10
140.50
173.33
210.70
CO
₂
(
±
0.5%)
Max Rate
%
9.76
10.20
9.40
9.30
9.40
9.62
9.44
Min Rate
%
8.56
8.60
8.60
8.70
8.60
8.98
8.51
NOx with O
₂
= 0% (gross)
Weighted
mg/kWh
34.1
33.2
35.2
34.9
34.8
33.9
35.7
Efficiency
Seasonal
%
96.7
96.2
96.4
97.2
96.7
96.6
96.7
*SEDBUK
2009
%
89.6
89.3
89.4
n/a
n/a
n/a
n/a
Operating Temperature
Max
˚C
85
MODEL
30/30P
40/40P
60/60P
80/80P
100/100P
120/120P
150
Gas Supply
2H - G20 - 20mbar / 3P - G31 - 37mbar
Gas Supply
Connection
G
¾
Flow Connection
G1
¼
Return Connection
G1
¼
Max Pressure
(sealed system)
Bar
(psi)
6
Maximum Static Head
m
61
Electricity Supply
230V - 50Hz
Fuse Rating
A
4.0
Power Consumption
W
81
138
82
149
187
243
240
IP Rating
IPX4D
Nominal Flue Size
(concentric)
mm
80/125*
100/150
Condensate Drain
mm
25
Water Content
l
3.0
5.0
7.0
9.2
Dry Weight
Kg
47.5
57.5
73
81
Weighted Power Level
dBA
55.2
57.7
59
59.9
62
62
59
BOILER
EVOMAX 2
Remote indication (run & alarm)
Hours run
BMS (0-10v) operation
Pump overrun
Large backlit LCD controls,
including 5 line plain text
display
Dynamic control menu set up
BOILER
EVOMAX 2
Multi boiler frame & header kits
(see pages 16-19)
Varican Module Master Kit
Varican Module Slave Kit
Extension Module Kit
OPENTHERM Room Control Kit
Room Sensor Kit
Tank Sensor Kit
Outside Sensor Kit
Header Flow Tank Immersion Sensor Kit
Header Flow Tank Strap On Sensor Kit
Safety Interlock Kit
0-10V Pump Control Kit
Condensate Pump
MODEL
30P
40P
60P
80P
100P
120P
Boiler Output (non-condensing)
Mean 70°
Max
kW
30
40
60
80
100
120
Min
kW
6
8
12
16
20
24
Boiler Output (condensing) Mean 40°C
Max
kW
30.9
41.2
62.1
82.6
101.7
123.3
Min
kW
6.4
8.3
12.4
16.8
21.3
25.7
Boiler Input Max Rate
Net
kW
30.4
40.5
60.7
81.9
102.4
122.9
Gross
kW
33
44
66
88.9
111.2
133.4
Boiler Input Min Rate
Net
kW
6.1
8.1
12.0
16.2
20.5
24.6
Gross
kW
6.6
8.8
13.1
17.5
22.2
26.7
Gas Rate
Max rate
m
³
/hr
1.26
1.69
2.53
3.41
4.35
5.23
Flue Gas Flow Rate
Max Rate
m
³
/hr
44.09
61.68
88.66
121.57
153.60
183.81
CO
₂
(
±
0.5%)
Max Rate
%
10.9
11.2
11.4
11.4
10.8
11.2
Min Rate
%
10.3
9.7
10.2
10.8
10.1
10.1
NOx with O
₂
= 0% (gross)
Weighted
mg/kWh
52.3
64.4
67.7
63.2
65.3
41.6
Efficiency
Seasonal
%
97.2
96.7
96.9
97.7
96.7
96.6
*SEDBUK
2009
%
90.6
90.3
90.5
n/a
n/a
n/a
Operating Temperature
Max
˚C
85