19
INSTALLATION
Ideal Logic Code Combi ES -
Installation and Servicing
FLUE OUTLET
16 CUTTINg & sETTINg ThE FLUE LENgTh
CUT 75MM OFF hORIzONTaL FLUE TERMINaL 1000MM LONg B paCK (TELEsCOpIC)
1. Measure cut flue length (A+44mm). (If required telescopic length is not between
658 and 708 then proceed to “Setting Telescopic Flue B Pack”).
2. Remove telescopic end piece from the flue body and set aside.
3. Mark the circumference 75mm from the open end of the outer flue.
4. Cut along the 75mm mark cutting
only the outer flue
ensuring the cut is square.
5. Dress the cut end to make sure all burr is removed and the cut edge is in its
original shape.
6. Measure 20mm from the newly cut edge of the outer flue, place a mark at the top of the flue approximately 20mm wide &
write stop the terminal side of the line.
7. Mark the inner tube 10mm longer than the outer tube around its circumference and cut following the mark to ensure its cut
square
8. Remove all burrs and place a chamfer on the outer edge to aid assembly.
9. Re-assemble telescopic section.
sETTINg TELEsCOpIC FLUE B paCK
1. Measure the required flue length (A+44mm).
2. Measure from the outer terminal lip to end of outer flue. Pull apart flue until
desired length is achieved. ENSURE THE STOP MARK IS NOT VISIBLE,
IF IT IS, THE FLUE IS TOO SHORT AND SHOULD NOT BE USED.
3. Check that both flue seams are at the top and the outlet terminal is upper
most.
4. Drill a 3.5mm hole through one of the 2 outer side holes in the outer flue
section into the inserted outer flue (as shown). Take care not to pierce the
inner plastic flue. Fit screw provided.
5. Seal the joint on the outer air duct with the tape provided.
6. Fit internal and external wall seals (see installing flue)
CUTTINg hORIzONTaL FLUE TERMINaL (600MM LONg) B paCK
1. Measure the required cut flue length (A+44mm). If inside the dimensions
shown in Figure 2 “1 Piece 600mm” proceed.
2. Measure from the outer terminal lip to end of outer flue. Mark the
required cut length (A+44) around the circumference of the outer flue and
cut following the mark to ensure its cut square.
3. Dress the cut end to make sure all burr’s are removed and the cut edge
is in its original shape.
4. Mark the inner tube 10mm longer than the outer tube around its
circumference and cut following the mark to ensure its cut square.
5. Remove all burrs and place a light chamfer on the outer edge to aid
assembly.
TELEsCOpIC FLUEs
TELEsCOpIC FLUE B paCK
SHOULD ONLy BE ADJUSTED FOR USE WITHIN ITS SPECIFIED RANGE AND MUST NOT
BE CUT
hORIzONTaL FLUE TERMINaL (1000MM LONg) B paCK (TELEsCOpIC)
MUST ONLy BE CUT IF REQUIRED FLUE
LENGTHS ARE BETWEEN
602
&
652MM
. THIS WILL REQUIRE 75MM TO BE CUT OFF THE TERMINAL END OF THE
1000MM TELESCOPIC FLUE.
ALL OTHER LENGTHS OBTAINED USING “D” PACK EXTENSIONS IN FLUE LENGTH TABLE 1, COLUMN “HORIZONTAL
FLUE TERMINAL (1000MM LONG) B PACK CUT 75MM” (TELESCOPIC) SHOULD HAVE THE 75MM CUT OFF THE “D”
PACK ExTENSION AND NOT TELESCOPIC FLUE
Содержание ES26
Страница 2: ...2 Ideal Logic Code Combi ES Installation and Servicing ...
Страница 59: ...59 Notes Ideal Logic Code Combi ES Installation and Servicing ...
Страница 60: ......